Nortec SE Series User Manual
Page 23
Installation | 20
Figure 16: Steam Distributor/SAM-e Below Humidifier (Hose Shown)
Figure 17: Steam Under Obstruction (Copper Steam Line Shown)
‘P’ Trap
Install Condensate Tee
Before Distributor
1 ft (30 cm)
min. Before
any bend
Min 12 in.
(30 cm)
radius
Hose will soften
over time
proper support
Is necessary
Support Brackets
1 ft (30 cm)
min.
‘P’ Trap
To drain
To drain
1ft (30 cm)
min. before
any bend
Obstruction
Use full size condensate tee
at low point. Slope lines up
to “T” and immediately after it.
1 ft (30 cm)
min.
1 ft (30 cm)
0.5 in. (1.2 cm) min.
To drain
To drain
‘P’ Trap
‘P’ Trap
See also other documents in the category Nortec Equipment:
- HumDigital (28 pages)
- NHDI Nortec OnLine (16 pages)
- SynPur (37 pages)
- Steam Distribution (15 pages)
- DRAABE Pure Water System (59 pages)
- AIRFOG Series (48 pages)
- NHDI Resistive Element (40 pages)
- LiveSteam v.1 (38 pages)
- OnLine NHRS (24 pages)
- SAM-e (62 pages)
- HP Series (76 pages)
- LINKS 2 SETC (50 pages)
- Outdoor Temperature Sensor (2 pages)
- Off Digital Wall Humidistat (4 pages)
- LINKS 2 SC (44 pages)
- Off Digital Duct Humidistat (4 pages)
- BLOWER PACK For RH Series (6 pages)
- Outdoor Mount Temperature Sensor (2 pages)
- SETC Outdoor (32 pages)
- Off Digital Wall & Duct Humidistat (6 pages)
- 2-10 V Wall & Duct Humidity Sensor (6 pages)
- Steam Distributors (16 pages)
- MES2 (54 pages)
- LINKS XPS SETC (68 pages)
- LINKS 2 GSTC B+ (23 pages)
- Modbus (52 pages)
- RH2+ (62 pages)
- Blower Packs (31 pages)
- LONWORKS (36 pages)
- Remote Interface (34 pages)
- NH-EL Series (99 pages)
- ME Direct Feed (40 pages)
- ME Control (76 pages)
- MLP RO pump station (12 pages)
- ME Control Installation (48 pages)
- Air Humidification System BS (30 pages)
- ME Direct Feed Installation (48 pages)