beautypg.com

Nortec SE Series User Manual

Page 61

background image

Operation | 58

(RH Settings Continued)

LIM Set-P
Sets the duct high limit setpoint
value. As RH in the duct approaches
the high limit the output of the
humidifier will be throttled back to
prevent wetting the duct. (Default =
80%)
LIM Band
Should not normally be changed. The
LIM Band setting adjusts the band
within which the humidifier will
throttle down the humidifier output
from 100 to 0%. (Default = 15%)


Limit Damping
Sets the number of seconds the
sensed RH must exceed the limit
band before output is throttled down.
(Default = 5 s)

RH Alerts
Sets whether the humidifier will
display warnings when humidity rises
above or falls below configured
limits. (Default = Off)

RH High
Sets the RH level above which the
humidity must rise before a warning
is generated. Warning is only
generated if RH Alerts is set to on.

RH Low
Sets the RH level below which the
humidity must fall before a warning
is generated . Warning is only
generated if RH Alerts is set to on.


Limit Set Point
80% RH

80% RH

Menu

Set

LIM Set-P

: 80%

80% RH

Limit Band
15% RH

15% RH

Menu

Set

LIM Band

: 15% RH

15% RH

Limit Damping
5 s

5 s

Menu

Set

LIM Damp

: 15% RH

5 s

RH Alerts
On
On
Off

Menu

Set

RH Alerts

: On

On

RH High
75% RH

75% RH

Menu

Set

RH High

: 75%

75% RH

RH Low
33% RH

33% RH

Menu

Set

RH Low

: 33% RH

33% RH