51 | Operation

User Defined Settings

The selections in User Defined Settings allow you to configure most user configurable features
available with the SETC. Press Set while highlighting User Defined Settings in the Main Menu.

Drain Cool
Selects whether drain water cooling
will be performed by adding fill water
to drain water. Off = fill valve not
activated during drain. On = fill valve
activated whenever drain pump is
on, Smart = fill valve only activated
with drain pump when tank is hot.
(Default = Smart)




Blowdown Rate
Sets the amount of water as a
percentage of steam produced that
will be drained to control mineral
concentration in the tank. (Default –
25%)

Full Tank Blowdown
Sets whether the tank will be
periodically flushed to help flush
minerals and scale. Blowdown
frequency is controlled by the FTBD
Hours parameter below. (Default =
On)
FTBD Time
Sets the time of day when a full tank
blow down will occur to avoid
interrupting humidifier operation
during critical times. (Default =
23:30)

FTBD Hours
Sets the number of hours between
full tank blow downs. Hours are
accumulated on a weighted basis (1
hour at 50% demand = 0.5 hrs).
(Default = 100 hr)

User Defined Settings
Drain Cool

: Off

BD Rate

: 25%

FTBD

: Off

FTBD Time

: Off

FTBD Hours

: 100

Idle Mode

: Idle Drain

Idle Time

: 72 hr

Fill Corr

: 100%

Drain Corr

: 100%

Float Ck

: 23:30

Date

: 06/27/09

Time

: 13:22

Unit

: lb/hr

Language

: English

Contrast

: 10

Leak Ck

: Off

Menu

Set

Drain Cool

: On

Drain Cool
On
Off
On
Smart

Menu

Set

On

BD Rate

: 25%

Blowdown Rate
25%


Menu

Set

25 %

FTBD Time

: Off

FTBD Time

Hour 23
Minute 30

Menu

Set

Hour 23

FTBD Hours

: 100f

FTBD Hours
100
100

Menu

Set

100

FTBD

: Off

Full Tank Blowdown
Off
On
On

Menu

Set

Off