73 general troubleshooting, 73 humidifier, General troubleshooting – Nortec SE Series User Manual

Page 76: Humidifier

background image

73 | Troubleshooting

General Troubleshooting

The following section provides general guidelines for troubleshooting the SETC/P humidifier and
auxiliary components. For detailed troubleshooting information refer to the manuals that were
provided with the auxiliary equipment, to Table 13: Troubleshooting Warnings and Faults, and to
Table 14: Troubleshooting SEP Faults later in this chapter.

Humidifier

Table 12: General Troubleshooting

Symptom

Cause

Corrective Action(s)

Nothing happens when On/Off
switch is turned on.

1 Fuse blown

1 Check inline fuse in yellow housing

between transformer and driver
board. Check and replace fuse on
driver board.

2 Incorrect or no Voltage

2a Check voltage against spec label and

correct.

2b Check disconnect and insure

humidifier is getting power.

3 Step Down Transformer not

outputting 24VAC

3 Replace the transformer

Humidifier will not humidify or
not reaching RH setpoint

1 Safety loop open

1a Check if green led is flashing on the

humidifier’s display.

1b Check if there is 24 VAC at terminal

2.

1c Check wiring and operation of On/Off

devices connected to terminal 1 and
2. Ensure they are closing when they
should be.

2 High limit limiting output

2 Check if the high limit is installed too

close to the humidifier and if it is
operating correctly.

3 No signal on Channel 1

3 Check voltage between terminal 3

and 4. For demand configuration
15% of full scale signal must be
present for humidifier to start. For
transducer configuration the signal
must be lower than setpoint for the
humidifier to start.

4 No signal on Channel 2
(For units configured for dual
channel operation).

4 Check voltage between terminal 5

and 3. For demand configuration 15%
of full scale signal must be present
for humidifier to operate. For
transducer configuration the signal
must be lower than setpoint for the
humidifier to start..

5 Capacity has been manually

limited

5 Check Manual Capacity on status

screens. Adjust “Manual Cap” in the
“Control Setting” menu if necessary.

Humidifier has faulted or has
a warning

1 Software has detected an

abnormal condition

1 Refer to Table 13troubleshooting

warnings and faults.