Nortec SE Series User Manual
Page 55
Operation | 52
(User Defined Settings Continued)
Idle Mode
Sets what the humidifier will do
during periods with no demand. Idle
Only = Do nothing. Idle Drain = Drain
the tank if there is no demand (wait
time set with idle Time parameter).
Keep Warm = periodically open CV
valve to keep tank warm. for a
demand and drain the tank if no
demand (Default = Idle Drain)
Idle Time
Sets the time without demand before
the Idle Drain function will drain the
tank (if activated). (Default = 72 hr)
Fill Correction
Increases or decreases the length of
fill valve pulses to compensate for
abnormal site conditions. (Default =
100%)
Drain Correction
Increases or decreases the length of
drains to compensate for abnormal
site conditions. (Default = 100%)
Float Check
Sets the time of day when a float
check to verify drains and float
operation will take place. Can also
disable the float check. (Default =
23:30 and On)
Date
Sets the date. Selecting Day, Month,
or year takes the user to a submenu
that allows the value to be increased
or decreased by pressing up/down
arrows. Set accepts the setting.
Idle Mode
: Idle Drain
Idle Mode
Idle Drain
Idle Only
Idle Drain
Keep Warm
Menu
Set
Idle Drain
Idle Time
: 72 hr
Idle Time
72 hr
72 hr
Menu
Set
72 hr
Fill Corr
: 100%
Fill Correction
100 %
100 %
Menu
Set
100 %
Drain Corr
: 100%
Drain Correction
100%
100 %
Menu
Set
100%
Float Ck
: 23:30
Float Ck
Hour
: 23
Minute
: 30
Status
: On
Menu
Set
Hour
: 23
Date
: 27/06/09
Date
Day
: 27
Month
: 06
Year
: 09
Menu
Set
Day
: 27