beautypg.com

Nortec SE Series User Manual

Page 83

background image

Troubleshooting | 80

Code

Display

Message

LED

System Detected

Cause

Corrective Action(s)

MTW

(Cont)

3 Humidifier configured

for Modbus but not
connected to network

3 Configure controls

correctly in “Control
Setting” level of
software (see Operation
Chapter).

4 Improper wire used

4 Use 120 Ohm

impedance shielded
twisted pair cable.

5 Noise preventing

humidifier from
detecting signal.

5 Eliminate source of

noise causing
interference.

NSW

No Signal

Warning

No
communication
is detected from
Master unit.
(This unit is set
up as slave)

1 Improper wiring

1 Check wiring

connections, polarity,
and type of wire used.
(See Staged Modulation
Wiring (SETC Only)
on
page 31)

RDW

Remote

Disabled

The unit has
been remotely
disabled through
modbus
communication
or Nortec
Online.

1 Network signal

received by humidifier
to shut down.

1 Normal operation for

humidifier on network
control Contact
network administrator
to enable humidifier.

RHW

Rh High

Warning

The measured
RH is above the
RH High alarm
setting.

1 Setpoint higher than

RH alarm setting

1 If the humidifier is still

operating then check
and adjust setpoints.

RLW

Rh Low

Warning

The measured
RH is below the
RH Low alarm
setting.

1 Humidifier not running

1 Check why humidifier is

not running and put it
into operation.

2 Setpoint lower than RH

low alarm setting

2 Check and adjust

setpoints.

RMW

Rh Limit
Warning

Operation is
interrupted until
an input higher
than 3% is
received.

1 Sensor not powered

1 Use multimeter to

check that sensor is
powered.

2 Sensor not wired

correctly

2 Check wiring is secure

and wired correctly per
instructions in
installation chapter.

3 Defective sensor

3 Check if sensor is

outputting
corresponding to RH. If
not replace the sensor.

4 RH less than 5%

4 RH less than 5% are

interpreted as a broken
sensor. Contact Nortec
Representative for
recommendation.