beautypg.com

T - command trigger mask, Sk…… 80 – Measurement Computing DAC488 v.1 User Manual

Page 86

background image

80 DAC488 Commands

DAC488 User’s Manual

T - Command Trigger Mask

TYPE

System Command

SYNTAX

Tmask

Set bit(s) in the Command Trigger Mask to specify which ports will be triggered by

the Trigger command (

@

). The mask bits are as follows (bit values are shown in

parenthesis):

Bit 1 = Enable DAC port 1 to trigger on

@

. (decimal 1)

Bit 2 = Enable DAC port 2 to trigger on

@

. (decimal 2)

Bit 3 = Enable DAC port 3 to trigger on

@

. (decimal 4) (DAC488/4 only)

Bit 4 = Enable DAC port 4 to trigger on

@

. (decimal 8) (DAC488/4 only)

T-mask

Clears the specified bits in the Command Trigger Mask.

T0

Clears all bits in the Command Trigger Mask.

T?

Returns current Command Trigger Mask.

DESCRIPTION

The Command Trigger Mask enables or disables the specified DAC port for triggering by the Trigger command (@).

Note:

The default bit value for each port is 0.

EXAMPLE

PRINT#1,"CLEAR09"

Line 1: Reset the DAC488.

PRINT#1,"OUTPUT09;C1 T1 P1

A0 R2 V4 X"

Line 2: Select Indirect Control mode, enable port 1 to trigger on @,

select port 1, disable autoranging, select

±

5 volt range, output 4 volts.

PRINT#1,"OUTPUT09;@"

Line 3: Trigger DAC port 2. The DAC488 will output 4 volts on port 1.

This manual is related to the following products: