Fuel Truck Controller Manual

70

Pump malfunction

Turn the Fuel Truck

Controller bypass switch

on, lift the nozzle and

check that the pump

supplies fuel

If the problem persist:
1. Check Handle-On

Switch

2. Repair pump

Handle-on switch

problem

Is the In Use red LED in

MPI-C board lit when

nozzle is lifted?

1. Check In Use cable and

repair, if necessary

2. Check Terminal wires

and repair, if necessary

3. Check The In Use

Switch in the pump and

repair, if necessary

Pump is

authorized but

Call state is not

detected (nozzle

icon in SiteOmat

Status screen

does not display

Call state)

Faulty in-use switch

in pump

Power off the pump, using

a ohmmeter measure the

switch in on and off states

Replace pump switch in

cases where no short was

detected

Faulty connections

Check In Use cable
Check In Use terminal

block connections

Make good electrical

connection if faulty one

exists

Faulty In Use

terminal block

Replace In-use terminal

block

Faulty MPI-C board Verify that the Call red

LED is lit when nozzle is

lifted

If the red LED is not lit,

replace MPI-C board.

If the led is lit, the problem

is external to the controller

Faulty 8-Port

Replace 8-Port

Pump is

authorized, pump

motor is running,

but no fuel is

supplied

Faulty solenoid

valve
Faulty pump

Does the pump solenoid

valve produce a clicking

sound?

1. Replace valve
2. Repair pump


Table 4-1. Fuel Truck Controller Troubleshooting (Cont'd)

Fault

Probable Cause

Checks

Corrective Action

Mechanic pump does not refuel (Continued)