AMETEK SLD Series User Manual
Page 63

Sorensen SLD-Series DC Load
Remote Programming
M540075-01 Rev C
5-9
LEVEL HIGH/LOW
Purpose:
Select Low or High level in static mode, of DC electronic loads.
Command Syntax:
LEVE {SP}{HIGH|LOW}{NL}
Description:
LEVE LOW is Set LOW current level in CC mode, LOW resistance level in CR mode, or LOW
voltage level in CV mode at the active load channel.
LEVE 1 is Set HIGH current level in CC mode, HIGH resistance level in CR mode, or HIGH voltage
level in CV mode at the active load channel.
PRESET ON/OFF
Purpose:
Set the upper or lower digit multi-function meter to display the programmed load level.
Command Syntax:
PRES{SP}{0|1|OFF|ON}{NL}
Description:
PRES ON is set the load to preset on status.
MODE
Purpose:
Select the operating mode of Electronic load module.
Command Syntax:
MODE{SP}{0|1|2|3|CC|CR|CV|CP}{NL}
Description:
MODE CC ; set the presently operating mode to Constant Current mode for all of the load module in
the SLH mainframe.
MODE CV ; set the presently operating mode to Constant Voltage mode.
MODE 1 ; set the presently operating mode to Constant Resistance mode.
MODE CP ; set the presently operation mode to Constant Power mode.
CLEAR status register
Purpose:
CLEar the PROT and ERR status byte registers.
Command Syntax:
All Modules:
CLER{NL}
Description:
CLER ; clear the PROT and ERR status byte register, the PROT and ERR status byte register will
indicate “0" after executing the CLER command.
STORE
Purpose:
STORE the load level and load status into the memory of the SLH-series electronic load.
Command Syntax: