DLM 600W Series

M362161-01 K

4-2

Switch Position

Function

OFF (Down) Position

ON (Up) Position

1

REM SNS

Local Sense

Remote Sense

2

Slave

Master or Standalone

Slave

3 Not

Used

4

IMON, 10V Select

0–5V Range

0–10V Range

5

VMON, 10V Select

0–5V Range

0–10V Range

6

OVP, 10V Select

0–5V Range

0–10V Range

7

I, 10V Select

0–5V Range

0–10V Range

8

V, 10V Select

0–5V Range

0–10V Range

Table 4–1. Setup Switch Functions

4.2.1

SETUP Switch Functions

The SETUP switch allows configuring the power supply to user requirements. The
following paragraphs describe the functions of the various switch positions:

REM SNS: Position-1, when ON, selects the REM SNS connector as the source of the
feedback signal used for regulating the output voltage. When OFF, selects internal
sense at the output terminals for the feedback signal.

SLAVE: Position-2, when ON: selects the unit to be a slave; the front panel voltage
display and voltage/curent mode indicators are blanked out; the OUTPUT switch will
turn on/off only the individual slave unit; and the PARALLEL I/O ports are configured for
slave operation. When OFF: selects the unit to be a master or for standalone operation;
the OUTPUT switch will turn ON/OFF all of the paralleled units; the PARALLEL I/O
ports are configured for master operation.

IMON, 10V–Select: Position-4, when ON, selects 0–10 VDC range for readback of
output current. When OFF, selects 0–5 VDC range for readback of output current.

VMON, 10V–Select: Position-5, when ON, selects 0–10 VDC range for readback of
output voltage. When OFF, selects 0–5 VDC range for readback of output voltage.

OVP, 10V–Select: Position-6, when ON, selects 0–10 VDC programming of OVP
threshold. When OFF, selects 0–5 VDC programming of OVP threshold.

10V–Select: Position-7, when ON, selects 0–10 VDC programming of output current.
When OFF, selects 0–5 VDC programming of output current.

V, 10V–Select: Position-8, when ON, selects 0–10 VDC programming of output
voltage. When OFF, selects 0–5 VDC programming of output voltage.