LINK Systems OmniLink 5000 User Manual
Page 114

8.6
Section 8.4 Diagnostic Leds
The system 5000 card rack provides the following Led indicators:
POWER CONNECTOR MODULE
+24v
This indicates the status of the fused +24 volt power supply. It should normally be on
(Green) and if off typically indicates an external connection is shorted to ground. If the
supply does not return to +24 volt after any external short has been removed, the +24v
fuse could be blown or a fault could exist in the power supply.
C/B
This amber led turns on when channel A of the press control energizes the CH A clutch
brake dual air valve.
C/B
This amber led turns on when channel B of the press control energizes the CH B
clutch/brake dual air valve.
LMC
This indicates the status of the Link Master Control Relay. It should normally be on
(Green) and is turned off by the press control if a fault condition or a Master Stop Input
occurs.
LOGIC MODULE
The following status Leds are provided independently for both channel A and channel B of the press
control.
RESET
This Red indicator turns on for approximately 1/2 sec when the power to the card rack is
applied. It should never turn on during normal running conditions, and if it does indicates
a fault on the logic module.
+5V
This indicates the status of the internal +5 volt supply. It should normally be on (Green)
and if off indicates a fault in the system 5000 card rack.
R/D MODULE
+12
This indicates the status of the internal +12 volt power supply. It should normally be on
(Green) and if off indicates a fault in the system 5000 card rack, the resolver/encoder
assembly, or it's field connections.
-12
This indicates the status of the internal -12 volt supply. It should normally be on (Green)
and if off indicates a fault in the system 5000 card rack.