corded and can be inspected at the same time. Alarm events are stored regard-
less of log level and can be inspected using panel C 27 (ANOMALY). Panel S
59 displays and allows the setting of the following parameters:
Recording level:
The selectable log recording levels range from 1 to 3.
Level 1: records the sensors deviations events
Level 2: records statistics (pH and EC averages, accumulations)
Level 3: records programs and controller status events
Consulting level:
Selectable log consulting level (from 1 to 3). This parameter allows the user to
select the log event categories (see above) that will be inspected on panel C 28.
This parameter can be also modified during log consulting sequence within
panel C 28.
5.9.10 SET PASSWORD – S 60
Disable password: N
New password: ---
SET PASSWORD S60
This panel allows the setting of a system password. Any changes that are made
to the settings of this panel require password authorization. This panel displays
and allows the setting of the following parameters:
Disable password:
Choosing Y for the “Disable password” option will allow free access to the
Fertigation Controller after every start-up sequence, while choosing N will
enable start-up after which password authorization will be required to view
display panels.
New password: New password input. Numeric format only.
NOTE: The function of the Fertigation Controller is not effected due to a failed or
successful password authorization process during log on.