To determine the total power that a power cable must carry, total the VA
requirements for all of the devices that will be drawing power from that cable,
including both modules and other devices.
To determine what gauge cable (in AWG or metric) will be required based on the
total distance of the power cabling, refer to the tables 3.1 and 3.2 for cabling
measured in AWG and in mm. If the wire gauge used is smaller than required,
improper operation of one of more modules will result. All data in these tables
assume an average wire temperature of +55°C.
Table 3.1 - Power Cabling Requirements in AWG
Load (VA)
Feet
10
15
20
25
30
40
55
75
100 130 180
200
35
22
22
22
22
22
22
22
22
22
22
22
22
40
22
22
22
22
22
22
22
22
22
22
22
20
55
22
22
22
22
22
22
22
22
22
22
20
20
65
22
22
22
22
22
22
22
22
22
20
20
18
70
22
22
22
22
22
22
22
22
22
20
18
18
75
22
22
22
22
22
22
22
22
22
20
18
18
90
22
22
22
22
22
22
22
22
20
20
18
18
100
22
22
22
22
22
22
22
22
20
18
18
16
105
22
22
22
22
22
22
22
20
20
18
18
16
115
22
22
22
22
22
22
22
20
20
18
16
16
135
22
22
22
22
22
22
22
20
18
18
16
16
145
22
22
22
22
22
22
20
20
18
18
16
16
150
22
22
22
22
22
22
20
20
18
16
16
16
155
22
22
22
22
22
22
20
20
18
16
16
14
165
22
22
22
22
22
22
20
18
18
16
16
14
185
22
22
22
22
22
22
20
18
18
16
14
14
215
22
22
22
22
22
20
20
18
16
16
14
14
230
22
22
22
22
22
20
18
18
16
16
14
14
235
22
22
22
22
22
20
18
18
16
14
14
14
250
22
22
22
22
22
20
18
18
16
14
14
12
C
22
22
22
22
20
20
18
16
16
14
14
12
295
22
22
22
22
20
20
18
16
16
14
12
12
300
22
22
22
22
20
18
18
16
16
14
12
12