Carrier 48SX024-048 User Manual
Page 7
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

52
49 9/16"
(1320.8) (1259.3)
REQ'D CLEARANCES FOR SERVICING in (mm)
Duct panel
Unit top ... .
Siete opposite ducts
Compressor access
(Except for NEC requirements)
REQ'D CLEARANCES TO COMBUSTIBLE MATE in (mm)
0
36 (914)
36 (914)
36 (914)
Maximum extension of overhangs
Unit top
Duct side of unit .
Side opposite ducts
Bottom of unit
Flue panel..........................
NEC REQ’D CLEARANCES in. (mm)
Between units, control box side
Unit and ungrounded surfaces, control box side
Unit and block or concrete walls and other grounded
surfaces, control box side
7/8 (22.2) OIA
CONTROL ENTRY
48 (1219)
14 (356)
. 0
9 (229)
. . 0
30 (762)
42 (1067)
36 (914)
42 (1067)
OPTIONAL RETURN
AIR OPENING
1 11/16'
(43.2)
^1 13/16"
(46.2)
17 1/16 -
I (433.9)
^OPTIONAL SUPPLY
AIR OPENING
1 5/8 (41 3) OIA
GAS ENTRY
1/2" - 14 NPT
GAS CONNECTION
REAR VIEW
LEFT 510E VIEW
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(Ib/kg)
lb
kg
A
B
C
D
48SX024040
208/230-1-60
357
163
110/50
56/25
136/62
55/25
48SX024060
208/230-1-60
369
168
113/51
59/27
139/63
58/26
48SX030040
208/230-1-60
360
164
103/47
72/33
124/56
61/28
48SX030060/080
208/230-1-60
372
169
106/48
75/34
127/58
64/29
48SX036060/080
208/230-1-60, 208/230-3-60, 460-3-60
390
177
100/45
90/41
123/56
77/35
48SX036100/120
208/230-1-60, 208/230-3-60, 460-3-60
402
183
103/47
93/42
127/57
80/36
UNIT
CENTER OF GRAVITY (In./mm)
X
Y
Z
48SX024040
26 57/674 9
20 17/512 3
14 96/380 0
48SX024060
26 51/673 3
20.22/513 6
14 96/380 0
48SX030040
26 90/683 3
21.09/535 7
14 96/380 0
48SX030060/080
26 83/681.5
21 11/536.2
14 96/380.0
48SX036060/080
26.99/685 5
21 14/537 0
14.96/380 0
48SX036100/120
26 92/683 8
21 14/537 0
14 96/380.0
LEGEND
CG
— Center of Gravity
MAT'L —
COND
— Condenser
NEC
—
LV
— Low Voltage
REQ’D —
Material
National Electrical Code
Required
NOTE: Clearances must be maintained to prevent recirculation of
air from outdoor-fan discharge
Fig. 7 — 48SX024-036 With Optional Base Rail, Unit Dimensions