beautypg.com

Step 10 — install electrical connections, A warning, A caution – Carrier 48SX024-048 User Manual

Page 18

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Step 10 — Install Electrical Connections

Fig. 20 — Vertical Discharge Cover Removed

Adhere to the following criteria when selecting, sizing,

and installing the duct system:

1. Units are shipped with all 4 duct openings covered. Re­

move appropriate panels for intended installation.

2.

Select and size ductwork, supply-air registers, and

return-air grilles according to American Society of
Heating, Refrigeration and Air Conditioning Engineers
(ASHRAE) recommendations.

3. Use flexible transition between rigid ductwork and unit

to prevent transmission of vibration. The transition may
be screwed or bolted to duct flanges. Use suitable gas­
kets to ensure weathertight and airtight seal.

4. All units must have field-supplied filters or accessory

filter rack installed in the return-air side of the unit. Rec­
ommended sizes for filters are shown in Tables 1 and 2.

5. Size all ductwork for maximum required airflow (either

heating or cooling) for unit being installed. Avoid abrupt
duct size increases or decreases or performance may be
affected.

6. Adequately insulate and weatherproof all ductwork

located outdoors. Insulate ducts passing through uncon­
ditioned space, and use vapor barrier in accordance with
latest issue of Sheet Metal and Air Conditioning
Contractors National Association (SMACNA) and Air
Conditioning Contractors of America (ACCA) mini­
mum installation standards for heating and air condition­
ing systems. Secure all ducts to building structure.

7. Flash, weatherproof, and vibration-isolate all openings

in building structure in accordance with local codes and
good building practices.

A

WARNING

The unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of per­

sonal injury if an electrical fault should occur. This ground
may consist of an electrical wire connected to the unit
ground lug in the control compartment, or conduit ap­
proved for electrical ground when installed in accor­
dance with NEC (National Electrical Code) ANSI/
NFPA (latest edition) (in Canada, Canadian Electrical
Code CSA [Canadian Standards Association] C22.1)
and local electrical codes. Do not use gas piping as an
electrical ground. Failure to adhere to this warning could
result in personal injury or death.

i

A

CAUTION

Failure to follow these precautions could result in dam­
age to the unit being installed:

1. Make all electrical connections in accordance with NEC

ANSI/NFPA (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical connec­
tions must be in accordance with CSA standard C22.1
Canadian Electrical Code Part 1 and applicable local codes.
Refer to unit wiring diagram.

2. Use only copper conductor for connections between field-

supplied electrical disconnect switch and unit. DO NOT

USE ALUMINUM WIRE.

3. Be sure that high-voltage power to unit is within oper­

ating voltage range indicated on unit rating plate.

4. Do not damage internal components when drilling through

any panel to mount electrical hardware, conduit, etc. On
3-phase units, ensure phases are balanced within 2 per­
cent. Consult local power company for correction of im­
proper voltage and/or phase imbalance.

HIGH-VOLTAGE CONNECTIONS - The unit must have
a separate electrical service with a field-supplied, water­
proof, disconnect switch mounted at, or within sight from,
the unit. Refer to the unit rating plate for maximum fuse/
circuit breaker size and minimum circuit amps (ampacity)
for wire sizing. See Table 4 for electrical data.

The field-supplied disconnect switch box may be mounted

on the unit over the high-voltage inlet hole when the
standard power and low-voltage entry points are used. See
Fig. 2-9 for acceptable location.

Standard Power Entry — Proceed as follows to complete
the high-voltage connections to the unit:

1. Connect ground lead to chassis ground connection when

using separate ground wire.

2. Run high-voltage leads into unit control box.
3. Locate black and yellow wires connected to line side of

contactor.

4. Cut wires at partition where they exit control box.
5. Strip back leads and connect to high voltage leads. On

3-phase units, blue wire is provided stripped back and
ready to connect to high voltage lead. See unit wiring
label and Fig. 21.

18