Table 9 — Required Suction-Tube Temperature (F)*
TEMP (F)
61.5
64.2
67.1
70.0
73.0
76.0
79.2
82.4
85.7
0
35
37
39
41
43
45
47
49
51
2
37
39
41
43
45
47
49
51
53
4
39
41
43
45
47
49
51
53
55
6
41
43
45
47
49
51
53
55
57
8
43
45
47
49
51
53
55
57
59
10
45
47
49
51
53
55
57
59
61
12
47
49
51
53
55
57
59
61
63
14
49
51
53
55
57
59
61
63
65
16
51
53
55
57
59
61
63
65
67
18
53
55
57
59
61
63
65
67
69
20
55
57
59
61
63
65
67
69
71
22
57
59
61
63
65
67
69
71
73
24
59
61
63
65
67
69
71
73
75
26
61
63
65
67
69
71
73
75
77
28
63
65
67
69
71
73
75
77
79
30
65
67
69
71
73
75
77
79
81
32
67
69
71
73
75
77
79
81
83
34
69
71
73
75
77
79
81
83
85
36
71
73
75
77
79
81
83
85
87
38
73
75
77
79
81
83
85
87
89
40
75
77
79
81
83
85
87
89
91
‘Temperature at suction service vaive
Table 10 — Dry-Coil Air Delivery* — Horizontal Discharge at 230 and 460 V - Unit 48SS
(Deduct 10% from Cfm and Watts for 208 V Operation)
UNIT
48SS
MOTOR
SPEED
AIR
DELIVERY
EXTERNAL STATIC PRESSURE (In. wg)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
018
Low
Watts
230
225
220
210
195
170
t
t
t
t
t
Cfm
760
745
725
695
640
540
t
t
t
t
t
High
Watts
t
t
t
t
270
235
200
t
t
t
t
Cfm
t
t
t
t
850
700
450
t
t
t
t
024,
030
Low
Watts
275
275
273
269
260
257
249
t
t
t
t
Cfm
857
835
802
782
745
717
663
t
t
t
t
Med
Watts
371
368
360
349
345
326
319
304
293
t
t
Cfm
1079
1063
1027
996
978
919
865
783
726
t
t
High
Watts
514
493
476
460
443
425
401
378
344
t
t
Cfm
1409
1383
1324
1282
1223
1156
1068
984
857
t
t
036
Low
Watts
473
447
427
418
395
367
346
337
323
t
t
Cfm
1253
1253
1172
1130
1047
946
865
829
768
t
t
Med
Watts
519
500
478
459
439
410
377
357
340
t
t
Cfm
1414
1366
1287
1234
1162
1074
920
829
743
t
t
High
Watts
667
634
609
593
564
541
506
469
436
422
t
Cfm
1734
1639
1563
1461
1370
1292
1157
960
829
743
t
042
Low
Watts
678
635
604
580
550
520
493
455
430
t
t
Cfm
1540
1515
1475
1430
1375
1280
1225
1128
1020
t
t
High
Watts
t
820
785
750
700
680
649
612
570
t
t
Cfm
t
1825
1750
1685
1610
1525
1485
1355
1215
t
t
048
Low
Watts
t
t
854
786
744
706
641
606
557
511
t
Cfm
t
t
. 2026
1905
1830
1752
1603
1513
1367
1228
t
High
Watts
t
t
t
905
846
824
804
748
683
637
t
Cfm
t
t
t
2025
1905
1830
1752
1603
1398
1228
t
060
Low
Watts
1000
991
970
925
904
875
849
830
819
t
t
Cfm
2125
2110
2085
2040
2009
1960
1900
1845
1775
t
t
Med
Watts
1355
1315
1265
1212
1158
1103
1045
987
925
880
t
Cfm
2480
2440
2388
2330
2266
2198
2125
2050
1968
1890
t
High
Watts
t
t
1435
1375
1310
1265
1175
1108
1010
915
t
Cfm
t
t
2509
2450
2386
2310
2235
2160
2083
1888
t
‘Air deiivery values are without air filter and are for dry coil. See Table 14 for wet coil pressure drop. Deduct field-supplied air filter pressure drop
and wet coil pressure drop to obtain external static pressure available for ducting.
tUnit air delivery is outside of operating range.
NOTE; Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator-coil icing
may occur at airflows below this point. Water blow-off may occur at airflows above 450 cfm per 12,000 Btuh of rated cooling capacity.
L