beautypg.com

A warning, Led indications – Carrier 48SX024-048 User Manual

Page 23

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Fig. 23 — Burner Assembly

Observe manifold pressure and proceed as follows to ad­

just gas input:

1. Remove cover screw over regulator adjustment screw

on gas valve.

2. Turn regulator adjustment screw clockwise to increase

gas input, or turn regulator adjustment screw counter­
clockwise to decrease input. Manifold pressure must be
between 3.4 and 3.6 in. wg.

A

WARNING

Unsafe operation of the unit may result if manifold
pressure is outside this range. Personal injury or unit
damage may result.

3. Replace cover screw cap on gas valve.

4. Turn off gas supply to unit. Remove manometer from

pressure tap and replace pipe plug on gas valve. Turn on
gas to unit and check for leaks.

Measure Manifold Pressure (Propane Units') — The main
burner orifices on a propane gas unit are sized for the unit
rated input when the manifold pressure is 3.5 in. wg.

Proceed as follows to adjust gas input on a propane gas

unit:

1. Turn off gas to unit.

2. Remove pipe plug on manifold (see Fig. 23), then con­

nect manometer at this point.

3. Turn on gas to unit.
4. Remove cover screw over regulator adjustment screw

on gas valve.

5. Adjust regulator adjustment screw for a manifold pres­

sure reading of 3.5 in. wg. Turn adjusting screw clock­
wise to increase manifold pressure, or turn adjusting screw
counterclockwise to decrease manifold pressure.

6. Replace cover screw.
7. Turn off gas to unit. Remove manometer from pressure

tap. Replace pipe plug on gas valve, then turn on gas to
unit. Check for leaks.

CHECK BURNER ELAME - With burner access panel
removed, observe the unit heating operation. Watch the burner
flames to see if they are light blue and soft in appearance,
and that the flames are approximately the same for each
burner. See Fig. 24. Refer to Maintenance section for in­
formation on burner removal.
AIRFLOW AND TEMPERATURE RISE - The heating
section for each size unit is designed and approved for heat­
ing operation within the temperature-rise range stamped on
the unit rating plate.

BURNER FLAME

Table 6 shows the approved temperature-rise range for

each heating input, and the air delivery cfm at various tem­
perature rises The heating operation airflow must produce
a temperature rise that falls within the approved range.

Refer to Maintenance section on page 39 to adjust heat­

ing airflow when required.

HEATING SEQUENCE OF OPERATION - See Fig. 25-30
and unit wiring label.

On a call for heating, terminal “W” of the thermostat is

energized, starting the induced-draft motor. When the hall-
effect sensor on the induced-draft motor senses that it has
reached the required speed, the burner sequence begins. The
indoor-fan motor is energized 45 seconds after flame is
established. When the thermostat is satisfied and “W” is
deenergized, the burners stop firing and the indoor-fan mo­
tor shuts off after a 45-second time-off delay.

A LED (light-emitting diode) indicator is provided on the

control board to monitor operation. The control board is lo­
cated by removing the burner access panel. During normal
operation, the LED is continuously on. See chart below for
error codes:

LED Indications

ERROR CODE

LED INDICATION

Normal Operation

On

Hardware Failure

Off

Fan On/Off Delay Modified

1 Flash

Limit Switch Fault

2 Flashes

Flame Sense Fault

3 Flashes

Five Consecutive Limit Switch Faults

4 Flashes

Ignition Lockout Fault

5 Flashes

Inducer Switch Fault

6 Flashes

Rollout Switch Fault

7 Flashes

Internal Control Fault

8 Flashes

NOTES:
1 There is a 3-second pause between error code displays.

2 If more than one error code exists, all applicable error codes will

be displayed in numerical sequence

3 This chart is on the wiring diagram located inside the burner ac­

cess panel.

23