APPENDIX III. FAN PERFORMANCE (cont.)

48TC**05

1 Phase

4 Ton Horizontal Supply

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Standard Static Option

Medium Static Option

1200

643

0.23

762

0.34

859

0.46

944

0.58

1020

0.71

1300

675

0.28

790

0.40

886

0.52

969

0.65

1044

0.78

1400

707

0.33

819

0.45

913

0.58

996

0.72

1070

0.86

1500

740

0.38

849

0.52

941

0.66

1023

0.80

1096

0.95

1600

773

0.45

879

0.59

970

0.73

1050

0.88

1123

1.04

1700

807

0.52

910

0.67

999

0.82

1078

0.98

1150

1.14

1800

841

0.59

942

0.75

1029

0.91

1106

1.08

1177

1.25

1900

875

0.68

974

0.85

1059

1.02

1135

1.19

1205

1.37

2000

910

0.77

1006

0.95

1090

1.13

1165

1.31

1234

1.49

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Medium Static Option

Field---Supplied Drive

1

1200

1089

0.84

1153

0.98

1213

1.12

---

---

---

---

1300

1113

0.92

1177

1.06

---

---

---

---

---

---

1400

1138

1.01

1201

1.15

---

---

---

---

---

---

1500

1163

1.10

---

---

---

---

---

---

---

---

1600

1189

1.20

---

---

---

---

---

---

---

---

1700

---

---

---

---

---

---

---

---

---

---

1800

---

---

---

---

---

---

---

---

---

---

1900

---

---

---

---

---

---

---

---

---

---

2000

---

---

---

---

---

---

---

---

---

---

NOTE: For more information, see General Fan Performance Notes on page 87.

Boldface indicates field---supplied drive is required.

1. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).

48TC**05

1 Phase

4 Ton Vertical Supply

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Standard Static Option

Medium Static Option

1200

666

0.26

778

0.37

871

0.47

952

0.57

1025

0.67

1300

701

0.31

810

0.43

901

0.54

981

0.65

1053

0.76

1400

737

0.36

842

0.49

931

0.62

1010

0.74

1081

0.86

1500

773

0.42

875

0.57

963

0.70

1040

0.84

1110

0.96

1600

810

0.49

909

0.65

994

0.79

1070

0.94

1140

1.08

1700

847

0.57

943

0.73

1027

0.89

1101

1.05

1170

1.20

1800

885

0.66

978

0.83

1060

1.00

1133

1.16

1200

1.32

1900

923

0.75

1014

0.94

1093

1.11

1165

1.29

1231

1.46

2000

962

0.85

1049

1.05

1127

1.24

1198

1.42

1263

1.61

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Medium Static Option

Field---Supplied Drive

1

1200

1093

0.77

1155

0.87

1213

0.96

1268

1.05

1321

1.14

1300

1119

0.87

1181

0.98

1239

1.08

1294

1.18

---

---

1400

1147

0.98

1208

1.09

---

---

---

---

---

---

1500

1175

1.09

---

---

---

---

---

---

---

---

1600

---

---

---

---

---

---

---

---

---

---

1700

---

---

---

---

---

---

---

---

---

---

1800

---

---

---

---

---

---

---

---

---

---

1900

---

---

---

---

---

---

---

---

---

---

2000

---

---

---

---

---

---

---

---

---

---

NOTE: For more information, see General Fan Performance Notes on page 87.

Boldface indicates field---supplied drive is required.

1. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).

48TC