beautypg.com

Caution – Carrier 48TCA04---A12 User Manual

Page 7

background image

7

6. Use a water hose or other suitable equipment to flush

down between the 2 coil sections to remove dirt and

debris. Clean the outer surfaces with a stiff brush in

the normal manner.

7. Secure inner and outer coil rows together with a

field--supplied fastener.

8. Reposition the outer coil section and remove the coil

corner post from between the top panel and center

post. Reinstall the coil corner post and replace all

screws.

Totaline Environmentally Sound Coil Cleaner

Application Equipment

S

2--1/2 gallon garden sprayer

S

Water rinse with low velocity spray nozzle

UNIT DAMAGE HAZARD
Failure to follow this caution may result in accelerated

corrosion of unit parts.
Harsh chemicals, household bleach or acid or basic

cleaners should not be used to clean outdoor or indoor

coils of any kind. These cleaners can be very difficult

to rinse out of the coil and can accelerate corrosion at

the fin/tube interface where dissimilar materials are in

contact. If there is dirt below the surface of the coil,

use the Totaline environmentally sound coil cleaner.

CAUTION

!

UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced

unit performance or unit shutdown.
High velocity water from a pressure washer, garden

hose, or compressed air should never be used to

clean a coil. The force of the water or air jet will

bend the fin edges and increase airside pressure drop.

CAUTION

!

Totaline Environmentally Sound Coil Cleaner

Application Instructions

1. Proper eye protection such as safety glasses is recom-

mended during mixing and application.

2. Remove all surface loaded fibers and dirt with a vacu-

um cleaner as described above.

3. Thoroughly wet finned surfaces with clean water and

a low velocity garden hose, being careful not to bend

fins.

4. Mix Totaline environmentally sound coil cleaner in a

2--1/2 gallon garden sprayer according to the instruc-

tions included with the cleaner. The optimum solution

temperature is 100_F.

NOTE: Do NOT USE water in excess of 130_F, as the
enzymatic activity will be destroyed.

5. Thoroughly apply Totaline environmentally sound

coil cleaner solution to all coil surfaces including

finned area, tube sheets and coil headers.

6. Hold garden sprayer nozzle close to finned areas and

apply cleaner with a vertical, up--and--down motion.

Avoid spraying in horizontal pattern to minimize po-

tential for fin damage.

7. Ensure cleaner thoroughly penetrates deep into finned

areas.

8. Interior and exterior finned areas must be thoroughly

cleaned.

9. Finned surfaces should remain wet with cleaning

solution for 10 minutes.

10. Ensure surfaces are not allowed to dry before rinsing.

Reapplying cleaner as needed to ensure 10--minute

saturation is achieved.

11. Thoroughly rinse all surfaces with low velocity clean

water using downward rinsing motion of water spray

nozzle. Protect fins from damage from the spray

nozzle.

Evaporator Coil

Cleaning the Evaporator Coil

1. Turn unit power off. Install lockout tag. Remove

evaporator coil access panel.

2. If economizer or two--position damper is installed, re-

move economizer by disconnecting Molex plug and

removing mounting screws.

3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dish-

washer detergent in a pressurized spray canister. Wash

both sides of coil and flush with clean water. For best

results, back--flush toward return--air section to re-

move foreign material. Flush condensate pan after

completion.

5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.

Evaporator Coil Metering Devices
The metering devices are multiple fixed--bore devices

(Acutrolt) swedged into the horizontal outlet tubes from

the liquid header, located at the entrance to each

evaporator coil circuit path. These are non--adjustable.

Service requires replacing the entire liquid header

assembly.

To check for possible blockage of one or more of these

metering devices, disconnect the supply fan contactor

(IFC) coil, then start the compressor and observe the

frosting pattern on the face of the evaporator coil. A frost

pattern should develop uniformly across the face of the

coil starting at each horizontal header tube. Failure to

develop frost at an outlet tube can indicate a plugged or a

missing orifice.

Refrigerant System Pressure Access Ports

There are two access ports in the system -- on the suction

tube near the compressor and on the discharge tube near

the compressor. These are brass fittings with black plastic

caps. The hose connection fittings are standard 1/4 SAE

male flare couplings.

The brass fittings are two--piece High Flow valves, with a

receptacle base brazed to the tubing and an integral

spring--closed check valve core screwed into the base.

48TC