connects to the RTU--MP must be routed through the

raceway built into the corner post as shown in Fig. 34.

The raceway provides the UL required clearance between

high-- and low--voltage wiring. Pass the control wires

through the hole provided in the corner post, then feed the

wires thorough the raceway to the RTU--MP. Connect to

the wires to the removable Phoenix connectors and then

reconnect the connectors to the board.

Space Temperature (SPT) Sensors

A field--supplied Carrier space temperature sensor is

required with the RTU--MP to monitor space temperature.

There are 3 sensors available for this application:

S

33ZCT55SPT, space temperature sensor with override

button

S

33ZCT56SPT, space temperature sensor with override

button and setpoint adjustment

S

33ZCT59SPT, space temperature sensor with LCD

(liquid crystal display) screen, override button, and

setpoint adjustment

Use 20 gauge wire to connect the sensor to the controller.

The wire is suitable for distances of up to 500 ft. Use a

three--conductor shielded cable for the sensor and setpoint

adjustment connections. If the setpoint adjustment

(slidebar) is not required, then an unshielded, 18 or 20

gauge, two--conductor, twisted pair cable may be used.

Connect T--55 -- See Fig. 43 for typical T--55 internal

connections. Connect the T--55 SEN terminals to

RTU--MP J20--1 and J20--2. See Fig. 61.

SEN

SEN

J20-1

J20-2

C08460

Fig. 61 -- RTU--MP T--55 Sensor Connections

Connect T--56 -- See Fig. 45 for T--56 internal

connections. Install a jumper between SEN and SET

terminals as illustrated. Connect T--56 terminals to

RTU--MP J20--1, J20--2 and J20--3 per Fig. 62.

SEN

J20-1

J20-2

SEN

SET

Jumper

J20-3

SET

C08461

Fig. 62 -- RTU--MP T--56 Sensor Connections

Connect T--59 -- The T--59 space sensor requires a

separate, isolated power supply of 24 VAC. See Fig. 61

for internal connections at the T--59. Connect the SEN

terminal (BLU) to RTU--MP J20--1. Connect the COM

terminal (BRN) to J20--2. Connect the SET terminal (STO

or BLK) to J20--3.

OR

SET

SEN

OPB

COM- PWR+

BLU (SPT)

BLK (STO)

24 VAC

SENSOR

WIRING

POWER
WIRING

BRN (COM)

NOTE: Must use a separate isolated transformer.

C07132

Fig. 63 -- Space Temperature Sensor Typical Wiring

(33ZCT59SPT)

Economizer controls —

Outdoor Air Enthalpy Control (PNO HH57AC077) --

The enthalpy control (HH57AC077) is available as a

field--installed accessory to be used with the EconoMi$er2

damper system. The outdoor air enthalpy sensor is part of

the enthalpy control. (The separate field--installed

accessory return air enthalpy sensor (HH57AC078) is

required for differential enthalpy control. See below.)

Locate the enthalpy control in the economizer hood.

Locate two GRA leads in the factory harness and connect

these leads to enthalpy control sensors 2 and 3. See Fig.

48. Connect the enthalpy control power input terminals to

economizer actuator power leads RED (connect to TR)

and BLK (connect to TR1).

The outdoor enthalpy changeover setpoint is set at the

enthalpy controller.

The enthalpy control receives the outdoor air enthalpy

from the outdoor air enthalpy sensor and provides a dry

contact switch input to the RTU--MP controller. A closed

contact indicates that outside air is preferred to the return

air. An open contact indicates that the economizer should

remain at minimum position.

Differential Enthalpy Control — Differential enthalpy

control is provided by sensing and comparing the outside

air and return air enthalpy conditions. Install the outdoor

air enthalpy control as described above. Add and install a

return air enthalpy sensor.

Return Air Enthalpy Sensor — Mount the return--air

enthalpy sensor (HH57AC078) in the return--air duct. The

48TC