Return Air without Economizer — The sampling tube is

located across the return air opening on the unit basepan.

See Fig. 19. The holes in the sampling tube face

downward, into the return air stream. The sampling tube is

connected via tubing to the return air sensor that is

mounted on a bracket high on the partition between return

filter and controller location. (This sensor is shipped in a

flat--mounting location. Installation requires that this

sensor be relocated to its operating location and the tubing

to the sampling tube be connected. See installation steps

below.)

Return Air Detector Sampling Tube

Controller module

Return Air Detector module
(shipping position shown)*

*RA detector must be moved from shipping position to operating position by installer

C07307

Fig. 19 -- Typical Return Air Detector Location

Return Air with Economizer — The sampling tube is

inserted through the side plates of the economizer

housing, placing it across the return air opening on the

unit basepan. See Fig. 20. The holes in the sampling tube

face downward, into the return air stream. The sampling

tube is connected via tubing to the return air sensor that is

mounted on a bracket high on the partition between return

filter and controller location. (This sensor is shipped in a

flat--mounting location. Installation requires that this

sensor be relocated to its operating location and the tubing

to the sampling tube be connected. See installation steps

below.)

Return Air
Sampling Tube

C08129

Fig. 20 -- Return Air Sampling Tube Location

Completing Installation of Return Air Smoke

Sensor:

Flexible
Exhaust Tubes

Screws

Sample Tube

C08126

Fig. 21 -- Return Air Detector Shipping Position

1. Unscrew the two screws holding the Return Air

Sensor detector plate. See Fig. 21. Save the screws.

2. Remove the Return Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing out-

wards and the sampling tube connection is on the bot-

tom. See Fig. 22.

4. Screw the sensor and detector plate into its operating

position using screws from Step 1. Make sure the

sampling tube connection is on the bottom and the ex-

haust tube is on the top. See Fig. 22.

5. Connect the flexible tube on the sampling inlet to the

sampling tube on the basepan.

6. For units with an economizer, the sampling tube is in-

tegrated into the economizer housing but the connec-

tion of the flexible tubing to the sampling tube is the

same.

C08127

Fig. 22 -- Return Air Sensor Operating Position

FIOP Smoke Detector Wiring and Response

All units: FIOP smoke detector is configured to

automatically shut down all unit operations when smoke

condition is detected. See Fig. 23, Smoke Detector

Wiring.

Highlight A: JMP 3 is factory--cut, transferring unit

control to smoke detector.

Highlight B: Smoke detector NC contact set will open on

smoke alarm condition, de--energizing the ORN

conductor.

48TC