beautypg.com

Fastener torque values – Carrier 48TCA04---A12 User Manual

Page 81

background image

81

If the calculated IAQ minimum position is greater than

the IAQ maximum damper position configuration then it

will be clamped to the configured value.
Demand Limit
If the RTU--MP receives a level 1 (one degree offset), 2

(two degree offset), or a 3 (4 degree offset) to the BACnet

demand limit variable, the controller will expand the

heating and cooling setpoints by the configured demand

limit setpoint value and remain in effect until the BACnet

demand limit variable receives a 0 value.

FASTENER TORQUE VALUES

See Table 32 for torque values.

Table 32 – Torque Values

Supply fan motor mounting

120 +/--- 12 in---lbs

Supply fan motor adjustment plate

120 +/--- 12 in---lbs

Motor pulley setscrew

72+/--- 5 in---lbs

Fan pulley setscrew

72+/--- 5 in---lbs

Blower wheel hub setscrew

72+/--- 5 in---lbs

Bearing locking collar setscrew

65---70 in---lbs

Compressor mounting bolts

65---75 in---lbs

Condenser fan motor mounting bolts

20 +/--- 2 in---lbs

Condenser fan hub setscrew

84 +/--- 12 in---lbs

48TC