direction. To determine whether or not compressor is

rotating in the proper direction:

1. Connect service gauges to suction and discharge pres-

sure fittings.

2. Energize the compressor.
3. The suction pressure should drop and the discharge

pressure should rise, as is normal on any start--up.

If the suction pressure does not drop and the discharge

pressure does not rise to normal levels:

4. Note that the evaporator fan is probably also rotating

in the wrong direction.

5. Turn off power to the unit and install lockout tag.
6. Reverse any two of the unit power leads.
7. Re--energize to the compressor. Check pressures.

The suction and discharge pressure levels should now

move to their normal start--up levels.
NOTE: When the compressor is rotating in the wrong
direction, the unit will make an elevated level of noise

and will not provide cooling.

Cooling

Set space thermostat to OFF position. To start unit, turn on

main power supply. Set system selector switch at COOL

position and fan switch at AUTO. position. Adjust

thermostat to a setting below room temperature.

Compressor starts on closure of contactor.

Check unit charge. Refer to Refrigerant Charge section.

Reset thermostat at a position above room temperature.

Compressor will shut off. Evaporator fan will shut off

after a 30--second delay.

To shut off unit, set system selector switch at OFF

position. Resetting thermostat at a position above room

temperature shuts unit off temporarily until space

temperature exceeds thermostat setting.

Main Burners

Main burners are factory set and should require no

adjustment.

To check ignition of main burners and heating controls,

move thermostat setpoint above room temperature and

verify that the burners light and evaporator fan is

energized. Check heating effect, then lower the thermostat

setting below the room temperature and verify that the

burners and evaporator fan turn off.

Refer to Tables 11 and 12 for the correct orifice to use at

high altitudes.

Heating

1. Purge gas supply line of air by opening union ahead

of the gas valve. If gas odor is detected, tighten union

and wait 5 minutes before proceeding.

2. Turn on electrical supply and manual gas valve.

3. Set system switch selector at HEAT position and fan

switch at AUTO. or ON position. Set heating temper-

ature lever above room temperature.

4. The induced--draft motor will start.
5. After a call for heating, the main burners should light

within 5 seconds. If the burner does not light, then

there is a 22--second delay before another 5--second

try. If the burner still does not light, the time delay is

repeated. If the burner does not light within 15

minutes, there is a lockout. To reset the control, break

the 24 v power to W1.

6. The evaporator--fan motor will turn on 45 seconds

after burner ignition.

7. The evaporator--fan motor will turn off in 45 seconds

after the thermostat temperature is satisfied.

8. Adjust airflow to obtain a temperature rise within the

range specified on the unit nameplate.

NOTE: The default value for the evaporator--fan motor
on/off delay is 45 seconds. The Integrated Gas Unit
Controller (IGC) modifies this value when abnormal limit

switch cycles occur. Based upon unit operating conditions,
the on delay can be reduced to 0 seconds and the off delay
can be extended to 180 seconds. When one flash of the
LED is observed, the evaporator--fan on/off delay has
been modified.
If the limit switch trips at the start of the heating cycle

during the evaporator on delay, the time period of the on

delay for the next cycle will be 5 seconds less than the

time at which the switch tripped. (Example: If the limit

switch trips at 30 seconds, the evaporator--fan on delay for

the next cycle will occur at 25 seconds.) To prevent

short--cycling, a 5--second reduction will only occur if a

minimum of 10 minutes has elapsed since the last call for

heating.

The evaporator--fan off delay can also be modified. Once

the call for heating has ended, there is a 10--minute period

during which the modification can occur. If the limit

switch trips during this period, the evaporator--fan off

delay will increase by 15 seconds. A maximum of 9 trips

can occur, extending the evaporator--fan off delay to 180

seconds.

To restore the original default value, reset the power to the

unit.

To shut off unit, set system selector switch at OFF

position. Resetting heating selector lever below room

temperature will temporarily shut unit off until space

temperature falls below thermostat setting.

Ventilation (Continuous Fan)

Set fan and system selector switches at ON and OFF

positions,

respectively.

Evaporator

fan

operates

continuously to provide constant air circulation. When the

evaporator--fan selector switch is turned to the OFF

position, there is a 30--second delay before the fan turns

off.

48TC