Carrier 48TCA04---A12 User Manual

Page 38

background image

38

Table 18 – Thermostat Mode

TB1 TERMINAL

FIELD CONNECTION

INPUT SIGNAL

1

RAT SEN

Analog (10k thermistor)

2

G

Discrete, 24VAC

3

RAT SEN

Analog (10k thermistor)

4

Y1

Discrete, 24VAC

5

6

Y2

Discrete, 24VAC

7

LOOP---PWR

Analog, 24VDC

8

W1

Discrete, 24VAC

9

IAQ---SEN

Analog, 4---20mA

10

W2

Discrete, 24VAC

11

IAQ---COM/OAQ---COM/RH---COM

Analog, 4---20mA

12

CCN + (RED)

Digital, 5VDC

13

OAQ---SEN/RH---SEN

Analog, 4---20mA

14

CCN Gnd (WHT)

Digital, 5VDC

15

AUX OUT (Power Exhaust)

(Output) Discrete 24VAC

16

CCN --- (BLK)

Digital, 5VDC

LEGEND:

CCN

---

Carrier Comfort Network (communication bus)

G

---

Thermostat Fan

IAQ

---

Indoor Air Quality (CO

2

)

OAQ

---

Outdoor Air Quality (CO

2

)

RAT

---

Return Air Temperature

RH

---

Relative Humidity

W1

---

Thermostat Heat Stage 1

W2

---

Thermostat Heat Stage 2

Y1

---

Thermostat Cool Stage 1

Y2

---

Thermostat Cool Stage 2

Connect T--56 -- See Fig. 45 for T--56 internal

connections. Install a jumper between SEN and SET

terminals as illustrated. Connect T--56 terminals to TB1

terminals 1, 3 and 5 (see Fig. 46).

2

3

4

5

6

1

SW1

SEN

SET

Cool

Warm

BRN (GND)

BLU (SPT)

RED(+)

WHT(GND)

BLK(-)

CCN COM

SENSOR WIRING

JUMPER
TERMINALS
AS SHOWN

BLK
(T56)

C08202

Fig. 45 -- T--56 Internal Connections

SEN

J6-7

J6-6

1

3

TB1

PL

SEN

SET

Jumper

TB1

PL

J6-5

5

SET

C08213

Fig. 46 -- PremierLink T--56 Sensor

Connect Thermostat — A 7--wire thermostat connection

requires a 24--v power source and a common connection.

Use the R and C terminals on the LCTB’s THERMOSTAT

connection strip for these. Connect the thermostat’s Y1,

Y2, W1, W2 and G terminals to PremierLink TB1 as

shown in Fig. 47.

G

J4-12

J4-10

J4-8

Y1

Y2

2

R

R

4

6

J4-6

J4-4

W2

C

8

10

C

SPACE
THERMOSTAT

PL

LCTB
THERMOSTAT

W1

TB1

LCTB
THERMOSTAT

C08119

Fig. 47 -- Space Thermostat Connections

If the 48TC unit has an economizer system and

free--cooling operation is required, a sensor representing

Return Air Temperature must also be connected

(field--supplied and installed). This sensor may be a T--55

Space Sensor (see Fig. 43) installed in the space or in the

return duct, or it may be sensor PNO 33ZCSENSAT,

installed in the return duct. Connect this sensor to TB1--1

and TB1--3 per Fig.

44. Temperature--resistance

characteristic is found in Table 15.

Configure the unit for Thermostat Mode — Connect to the

CCN bus using a CCN service tool and navigate to

48TC