Carrier 48TCA04---A12 User Manual

Page 72

background image

72

During free cooling operation, a supply air temperature

(SAT) above 50_F will cause the dampers to modulate

between Minimum Position setpoint and 100% open. With

SAT from 50_F to 45_F, the dampers will maintain at the

Minimum Position setting. With SAT below 45_F, the

outside air dampers will be closed. When SAT rises to

48_F, the dampers will re--open to Minimum Position

setting.

Should 100% outside air not be capable of satisfying the

space temperature, space temperature will rise until Y2 is

closed. The economizer control will call for compressor

operation. Dampers will modulate to maintain SAT at 50

to 55_F concurrent with compressor operation. The Low

Ambient Lockout Thermostat will block compressor

operation with economizer operation below 42_F outside

air temperature.

When space temperature demand is satisfied (thermostat

Y1 opens), the dampers will return to Minimum Damper

position if indoor fan is running or fully closed if fan is

off.

If accessory power exhaust is installed, the power exhaust

fan motors will be energized by the economizer control as

the dampers open above the PE--On setpoint and will be

de--energized as the dampers close below the PE--On

setpoint.

Damper movement from full closed to full open (or vice

versa) will take between 1--1/2 and 2--1/2 minutes.

Heating With EconoMi$er IV

During Occupied mode operation, indoor fan operation

will be accompanied by economizer dampers moving to

Minimum Position setpoint for ventilation. If indoor fan is

off, dampers will close. During Unoccupied mode

operation, dampers will remain closed unless a DCV

demand is received.

When the room temperature calls for heat (W1 closes), the

heating controls are energized as described in Heating,

Unit Without Economizer above.

PremierLink Control

THERMOSTAT MODE — If the PremierLink controller

is configured for Thermostat mode (TSTAT), it will

control only to the thermostat inputs on J4. These inputs

can be overridden through CCN communication via the

CV_TSTAT points display table. When in this mode, the

fire safety shutdown (FSD) input cannot be used, so any

fire/life safety shutdown must be physically wired to

disable the 24 vac control circuit to the unit.

Indoor Fan — The indoor fan output will be energized

whenever there is 24 vac present on the G input. The

indoor fan will be turned on without any delay and the

economizer damper will open to its minimum position if

the unit has a damper connected to the controller. This

will also occur if the PremierLink controller has been

configured for electric heat or heat pump operation.

Cooling — For cooling operation, there must be 24 vac

present on G. When G is active, the PremierLink

controller will then determine if outdoor conditions are

suitable for economizer cooling when an economizer

damper is available. A valid OAT, SPT (CCN space

temperature) and SAT (supply air temperature) sensor

MUST be installed for proper economizer operation. It

recommended that an outdoor or differential enthalpy

sensor also be installed. If one is not present, then a

jumper is needed on the ENTH input on J4, which will

indicate that the enthalpy will always be low. Economizer

operation will be based only on outdoor air dry bulb

temperature. The conditions are suitable when: enthalpy is

low, OAT is less than OATL High Lockout for TSTAT,

and OAT is less than OATMAX, the high setpoint for free

cooling. The default for OATL is 65_F. The default for

OATMAX is 75_F.

When all of the above conditions are satisfied and all the

required sensors are installed, the PremierLink controller

will use the economizer for cooling. One of three different

control routines will be used depending on the

temperature of the outside air. The routines use a PID loop

to control the SAT to a supply air setpoint (SASP) based

on the error from setpoint (SASPSAT). The SASP is

determined by the routine.

If an economizer is not available or the conditions are not

met for the following economizer routines below, the

compressors 1 and 2 will be cycled based on Y1 and Y2

inputs respectively.

Any time the compressors are running, the PremierLink

controller will lock out the compressors if the SAT

becomes too low. These user configurable settings are

found in the SERVICE configuration table:

Compressor 1 Lockout at SAT < SATLO1 (50 to 65_F)

(default is 55_F)

Compressor 2 Lockout at SAT < SATLO2 (45 to 55_F)

(default is 50_F)

After a compressor is locked out, it may be started again

after a normal time--guard period and the supply--air

temperature has increased at least 8_F above the lockout

setpoint.

Routine No. 1: If the OAT ≤ DXLOCK (OAT DX lockout

temperature) and DX Cooling Lockout is enabled when

Y1 input is energized, the economizer will be modulated

to maintain SAT at the Supply Air Setpoint (SASP) =

SATLO1 + 3_F (Supply Air Low Temp lockout for

compressor 1). When Y2 is energized, the economizer

will be modulated to control to a lower SASP = SATLO2

+ 3_F (Supply Air Low Temp lockout for compressor no.

2). Mechanical cooling is locked out and will not be

energized.

Routine No. 2: If DXLOCK (or DX Cooling Lockout is

disabled) < OAT ≤ 68_F when Y1 input is energized, the

economizer will be modulated to maintain SAT at SASP =

SATLO1 + 3_F. If the SAT > SASP + 5_F and the

economizer position > 85% then the economizer will

close the to minimum position for three minutes or until

the SAT > 68_F. The economizer integrator will then be

reset and begin modulating to maintain the SASP after

stage one has been energized for 90 seconds.