Table 14 – IGC Board LED Alarm Codes

LED

FLASH

CODE

DESCRIPTION

ACTION TAKEN BY

CONTROL

RESET METHOD

PROBABLE CAUSE

On

Normal Operation

Off

Hardware Failure

No gas heating.

Loss of power to the IGC. Check 5 amp

fuse on IGC, power to unit, 24V circuit

breaker, transformer, and wiring to the

IGC.

2

Flashes Limit Switch Fault

Gas valve and igniter

Off.

Indoor fan and inducer

On.

Limit switch closed,

or heat call (W) Off.

High temperature limit switch is open.

Check the operation of the indoor (evapo-

rator) fan motor.

Ensure that the supply-air temperature

rise is within the range on the unit name-

plate. Check wiring and limit switch opera-

tion.

3

Flashes Flame Sense Fault

Indoor fan and inducer

On.

Flame sense normal.

Power reset for LED

reset.

The IGC sensed a flame when the gas

valve should be closed. Check wiring,

flame sensor, and gas valve operation.

4

Flashes

Four Consecutive Limit

Switch Fault

No gas heating.

Heat call (W) Off.

Power reset for LED

reset.

4 consecutive limit switch faults within a

single call for heat. See Limit Switch Fault.

5

Flashes Ignition Fault

No gas heating.

Heat call (W) Off.

Power reset for LED

reset.

Unit unsuccessfully attempted ignition for

15 minutes. Check igniter and flame sen-

sor electrode spacing, gaps, etc. Check

flame sense and igniter wiring. Check gas

valve operation and gas supply. Check

gas valve connections to IGC terminals.

BRN lead must be on Pin 11.

6

Flashes

Induced Draft Motor

Fault

If heat off: no gas

heating.

If heat on: gas valve

Off and inducer On.

Inducer sense nor-

mal, or heat call (W)

Off.

Inducer sense On when heat call Off, or

inducer sense Off when heat call On.

Check wiring, voltage, and operation of

IGC motor. Check speed sensor wiring to

IGC.

7

Flashes Rollout Switch Lockout

Gas valve and igniter

Off.

Indoor fan and inducer

On.

Power reset.

Rollout switch has opened. Check gas

valve operation. Check induced-draft

blower wheel is properly secured to motor

shaft.

8

Flashes Internal Control Lockout No gas heating.

Power reset.

IGC has sensed internal hardware or soft-

ware error. If fault is not cleared by reset-

ting 24 v power, replace the IGC.

9

Flashes

Temporary Software

Lockout

No gas heating.

1 hour auto reset, or

power reset.

Electrical interference is disrupting the

IGC software.

LEGEND

IGC --- Integrated Gas Unit Control

LED --- Light---Emitting Diode

NOTES:

1. There is a 3---second pause between alarm code displays.
2. If more than one alarm code exists, all applicable alarm codes will be displayed in numerical sequence.
3. Alarm codes on the IGC will be lost if power to the unit is interrupted.