beautypg.com

Carrier 48TCA04---A12 User Manual

Page 47

background image

47

return air sensor is wired to the enthalpy controller

(HH57AC077). See Fig. 49.

To wire the return air enthalpy sensor, perform the

following:

1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable

to connect the return air enthalpy sensor to the enthal-

py controller.

2. At the enthalpy control remove the factory--installed

resistor from the (SR) and (+) terminals.

3. Connect the field--supplied RED wire to (+) spade

connector on the return air enthalpy sensor and the

(SR+) terminal on the enthalpy controller. Connect

the BLK wire to (S) spade connector on the return air

enthalpy sensor and the (SR) terminal on the enthalpy

controller.

NOTE: The enthalpy control must be set to the “D”
setting for differential enthalpy control to work properly.
The enthalpy control receives the indoor and return

enthalpy from the outdoor and return air enthalpy sensors

and provides a dry contact switch input to the RTU--MP

controller. A closed contact indicates that outside air is

preferred to the return air. An open contact indicates that

the economizer should remain at minimum position.

Indoor Air Quality (CO

2

sensor) — The indoor air quality

sensor accessory monitors space carbon dioxide (CO

2

)

levels. This information is used to monitor IAQ levels.

Several types of sensors are available, for wall mounting

in the space or in return duct, with and without LCD

display, and in combination with space temperature

sensors. Sensors use infrared technology to measure the

levels of CO

2

present in the space air.

The CO

2

sensors are all factory set for a range of 0 to

2000 ppm and a linear mA output of 4 to 20. Refer to the

instructions supplied with the CO

2

sensor for electrical

requirements and terminal locations. See Fig. 50 for

typical CO

2

sensor wiring schematic.

To accurately monitor the quality of the air in the

conditioned air space, locate the sensor near a return--air

grille (if present) so it senses the concentration of CO

2

leaving the space. The sensor should be mounted in a

location to avoid direct breath contact.

Do not mount the IAQ sensor in drafty areas such as near

supply ducts, open windows, fans, or over heat sources.

Allow at least 3 ft (0.9 m) between the sensor and any

corner. Avoid mounting the sensor where it is influenced

by the supply air; the sensor gives inaccurate readings if

the supply air is blown directly onto the sensor or if the

supply air does not have a chance to mix with the room air

before it is drawn into the return airstream.

Wiring the Indoor Air Quality Sensor —

For each sensor, use two 2--conductor 18 AWG (American

Wire Gage) twisted--pair cables (unshielded) to connect

the separate isolated 24 vac power source to the sensor

and to connect the sensor to the control board terminals.

To connect the sensor to the control, identify the positive

(4 to 20 mA) and ground (SIG COM) terminals on the

sensor. See Fig. 50. Connect the 4--20 mA terminal to

terminal TB1--9 and connect the SIG COM terminal to

terminal TB1--7. See Fig. 64.

SEN

COM

J4-2

J4-3

IAQ Sensor

24 VAC

C08462

Fig. 64 -- RTU--MP / Indoor CO

2

Sensor

(33ZCSENCO2) Connections

Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus

weatherproof enclosure) — The outdoor air CO

2

sensor is

designed to monitor carbon dioxide (CO

2

) levels in the

outside ventilation air and interface with the ventilation

damper in an HVAC system. The OAQ sensor is packaged

with an outdoor cover. See Fig. 52. The outdoor air CO

2

sensor must be located in the economizer outside air hood.

Wiring the Outdoor Air CO

2

Sensor — A dedicated power

supply is required for this sensor. A two--wire cable is

required to wire the dedicated power supply for the sensor.

The two wires should be connected to the power supply

and terminals 1 and 2.

To connect the sensor to the control, identify the positive

(4 to 20 mA) and ground (SIG COM) terminals on the

OAQ sensor. See Fig. 50. Connect the 4 to 20 mA

terminal to 48TC’s terminal TB1--11. Connect the SIG

COM terminal to 48TC’s terminal TB1--13. See Fig. 65.

SEN

COM

J4-5

J4-6

OAQ Sensor/RH Sensor

24 VAC

C08463

Fig. 65 -- RTU--MP / Outdoor CO

2

Sensor

(33ZCSENCO2) Connections

On 48TC units equipped with factory--installed Smoke

Detector(s), the smoke detector controller implements the

unit shutdown through its NC contact set connected to the

unit’s LCTB input. The FSD function is initiated via the

smoke detector’s Alarm NO contact set. The PremierLink

communicates the smoke detector’s tripped status to the

CCN building control. See Fig. 23 for unit smoke detector

wiring.

The

Fire

Shutdown

Switch

configuration,

MENU

Config

Inputs

input

5,

identifies

the

normally open status of this input when there is no fire

alarm.

48TC