provided in the EconoMi$er IV wiring harness. (See Fig.

70.)

ECONOMI$ERIV

ECONOMI$ERIV
CONTROLLER

GROMMET

RETURN AIR
SENSOR

RETURN DUCT
(FIELD-PROVIDED)

C07085

Fig. 79 -- Return Air Temperature or Enthalpy Sensor

Mounting Location

In this mode of operation, the outdoor-air temperature is

compared to the return-air temperature and the lower

temperature airstream is used for cooling. When using this

mode of changeover control, turn the enthalpy setpoint

potentiometer fully clockwise to the D setting. (See Fig.

76.)
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part

number HH57AC078) is required. Replace the standard

outdoor dry bulb temperature sensor with the accessory

enthalpy sensor in the same mounting location. (See Fig.

79.) When the outdoor air enthalpy rises above the

outdoor enthalpy changeover setpoint, the outdoor-air

damper moves to its minimum position. The outdoor

enthalpy changeover setpoint is set with the outdoor

enthalpy setpoint potentiometer on the EconoMi$er IV

controller. The setpoints are A, B, C, and D. (See Fig. 80.)

The factory-installed 620-ohm jumper must be in place

across terminals S

R

and SR+ on the EconoMi$er IV

controller.

CONTROL

CURVE

A
B
C
D

CONTROL POINT

APPROX.

deg. F (deg. C)

AT 50% RH

73 (23)
70 (21)
67 (19)
63 (17)

12

1

4

16

18

20

22

24

26

28

30

32

3

4

36

38

40

42

44

46

9

0

1

0

0

80

70

6

0

50

40

30

20

10

ENTHALPY BTU PER POUND DRY AIR

85

(29)

90

(32)

95

(35)

100

(38)

105

(41)

110

(43)

35

(2)

35

(2)

40

(4)

40

(4)

105

(41)

110

(43)

45

(7)

45

(7)

50

(10)

50

(10)

55

(13)

55

(13)

60

(16)

60

(16)

65

(18)

65

(18)

70

(21)

70

(21)

75

(24)

75

(24)

80

(27)

80

(27)

85

(29)

90

(32)

95

(35)

100

(38)

A

A

B

B

C

C

D

D

RELATIVE HUMIDITY (%)

HIGH LIMIT

CURVE

APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)

C06037

Fig. 80 -- Enthalpy Changeover Setpoints

48TC