beautypg.com

Carrier 48TCA04---A12 User Manual

Page 39

background image

39

PremierLink Configuration screen for Operating Mode.

Default setting is Sensor Mode (value 1). Change the

value to 0 to reconfigure the controller for Thermostat

Mode.

When the PremierLink is configured for Thermostat

Mode, these functions are not available: Fire Shutdown

(FSD), Remote Occupied (RMTOCC), Compressor Safety

(CMPSAFE), Supply Fan Status (SFS), and Filter Pressure

Switch (FILTER).

Economizer controls —

Outdoor Air Enthalpy Control (PNO HH57AC077) --

The enthalpy control (HH57AC077) is available as a

field--installed accessory to be used with the EconoMi$er2

damper system. The outdoor air enthalpy sensor is part of

the enthalpy control. (The separate field--installed

accessory return air enthalpy sensor (HH57AC078) is

required for differential enthalpy control. See below.)

Locate the enthalpy control in the economizer hood.

Locate two GRA leads in the factory harness and connect

these leads to enthalpy control sensors 2 and 3. See Fig.

48. Connect the enthalpy control power input terminals to

economizer actuator power leads RED (connect to TR)

and BLK (connect to TR1).

6

7

LCTB
ECON

3

2

Enthalpy
Switch

GRA

GRA

Factory Wiring Harness

C08218

Fig. 48 -- Enthalpy Switch (HH57AC077) Connections

The outdoor enthalpy changeover setpoint is set at the

enthalpy controller.

The enthalpy control receives the outdoor air enthalpy

from the outdoor air enthalpy sensor and provides a dry

contact switch input to the PremierLink controller. A

closed contact indicates that outside air is preferred to the

return air. An open contact indicates that the economizer

should remain at minimum position.

Differential Enthalpy Control — Differential enthalpy

control is provided by sensing and comparing the outside

air and return air enthalpy conditions. Install the outdoor

air enthalpy control as described above. Add and install a

return air enthalpy sensor.

Return Air Enthalpy Sensor — Mount the return--air

enthalpy sensor (HH57AC078) in the return--air duct. The

return air sensor is wired to the enthalpy controller

(HH57AC077). See Fig. 49.

LED

A

B

C

D

TR

TR1

SO

SR

2

3

1

+

+

BRN

RED

GRAY/ORN

GRAY/RED

WIRE HARNESS

IN UNIT

BLK

RED

S

+

(RETURN AIR

ENTHALPY

SENSOR)

S

+

(OUTDOOR

AIR

ENTHALPY

SENSOR)

ENTHALPY CONTROLLER

NOTES:

1. Remove factory-installed jumper across SR and + before connecting

wires from return air sensor.

2. Switches shown in high outdoor air enthalpy state. Terminals 2 and 3

close on low outdoor air enthalpy relative to indoor air enthalpy.

3. Remove sensor mounted on back of control and locate in outside air-

stream.

C06019

Fig. 49 -- Outside and Return Air Enthalpy Sensor

Wiring

To wire the return air enthalpy sensor, perform the

following:

1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable

to connect the return air enthalpy sensor to the enthal-

py controller.

2. At the enthalpy control remove the factory--installed

resistor from the (SR) and (+) terminals.

3. Connect the field--supplied RED wire to (+) spade

connector on the return air enthalpy sensor and the

(SR+) terminal on the enthalpy controller. Connect

the BLK wire to (S) spade connector on the return air

enthalpy sensor and the (SR) terminal on the enthalpy

controller.

NOTE: The enthalpy control must be set to the “D”

setting for differential enthalpy control to work properly.
The enthalpy control receives the indoor and return

enthalpy from the outdoor and return air enthalpy sensors

and provides a dry contact switch input to the

PremierLink controller. A closed contact indicates that

outside air is preferred to the return air. An open contact

indicates that the economizer should remain at minimum

position.

Indoor Air Quality (CO

2

sensor) — The indoor air quality

sensor accessory monitors space carbon dioxide (CO

2

)

levels. This information is used to monitor IAQ levels.

Several types of sensors are available, for wall mounting

in the space or in return duct, with and without LCD

display, and in combination with space temperature

sensors. Sensors use infrared technology to measure the

levels of CO

2

present in the space air.

The CO

2

sensors are all factory set for a range of 0 to

2000 ppm and a linear mA output of 4 to 20. Refer to the

instructions supplied with the CO

2

sensor for electrical

48TC