Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual
Page 32

32
R6GP-120*-235C
HSD kits:
920395 (208-230V, 3Ø, 60 Hz)
920396 (460V, 3Ø, 60 Hz)
Horizontal Flow Performance Chart*
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open ‡
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.9
CFM
RPM
kW
1.0
CFM
RPM
kW
1.1
CFM
4692
RPM
969
kW
2.75
1.2
CFM
4492
RPM
973
kW
2.61
1.3
CFM
4535
4305
RPM
998
976
kW
2.79
2.52
1.4
CFM
4569
4318
4066
RPM
1022
1001
980
kW
2.92
2.66
2.39
1.5
CFM
4308
4054
3799
RPM
1027
1006
984
kW
2.76
2.49
2.22
1.6
CFM
4368
4084
3797
3510
RPM
1050
1030
1009
988
kW
2.89
2.61
2.34
2.07
1.7
CFM
4422
4120
3817
3493
RPM
1071
1053
1034
1014
kW
3.03
2.74
2.44
2.17
1.8
CFM
4177
3875
3573
RPM
1075
1056
1037
kW
2.89
2.58
2.27
1.9
CFM
4127
3908
3296
RPM
1098
1079
1063
kW
2.96
2.72
2.31
2.0
CFM
4115
3866
3616
RPM
1118
1101
1083
kW
3.01
2.76
2.51
*
Requires horizontal conversion kit. Please refer to unit TSL for kit number.
Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 28. Blower Performance for R6GP-120*-235C Units
(10 Ton Horizontal Models Only)