Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual
Page 22
22
P6SP-090*
HSD kits:
920559 (208-230V, 3Ø, 60 Hz)
920558 (460V, 3Ø, 60 Hz)
Horizontal Flow Performance Chart*
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open ‡
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
1.2
CFM
RPM
kW
1.3
CFM
3397
3341
3284
RPM
1178
1171
1163
kW
2.34
2.20
2.06
1.4
CFM
3303
3210
3117
RPM
1192
1181
1169
kW
2.24
2.10
1.96
1.5
CFM
3434
3214
3065
2916
RPM
1233
1205
1189
1173
kW
2.44
2.15
2.00
1.85
1.6
CFM
3296
3098
2911
2723
RPM
1241
1217
1197
1177
kW
2.33
2.11
1.90
1.68
1.7
CFM
3406
3168
2929
2717
2505
RPM
1278
1252
1226
1204
1181
kW
2.52
2.27
2.01
1.79
1.57
1.8
CFM
3240
3000
2759
RPM
1285
1258
1231
kW
2.41
2.14
1.87
1.9
CFM
3334
3088
2869
RPM
1316
1289
1266
kW
2.56
2.25
2.00
2.0
CFM
3435
3178
2921
RPM
1347
1321
1294
kW
2.73
2.44
2.15
*
Requires horizontal conversion kit. Please refer to unit TSL for kit number.
Values includes losses for: Unit Casing, 2” Disposable Filters & Dry Evaporator Coil
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
Deduct 250 Cfm for electric heater kits
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 18. Blower Performance for P6SP-090* Units
(7.5 Ton Horizontal Models Only)