Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual
Page 12
12
P6SP-072*
MSD kits:
920609 (208-230V, 3Ø, 60 Hz)
920560 (460V, 3Ø, 60 Hz)
Horizontal Flow Performance Chart*
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open ‡
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.8
CFM
RPM
kW
0.9
CFM
2716
2500
2284
RPM
985
956
926
kW
1.17
1.05
0.93
1.0
CFM
2677
2491
2250
RPM
1012
987
959
kW
1.23
1.09
0.94
1.1
CFM
2682
2469
2255
RPM
1039
1015
990
kW
1.29
1.13
0.98
1.2
CFM
2663
2452
RPM
1067
1041
kW
1.35
1.18
1.3
CFM
2710
2465
2219
RPM
1096
1071
1046
kW
1.45
1.26
1.07
1.4
CFM
2675
2492
RPM
1126
1100
kW
1.47
1.33
1.5
CFM
2487
2195
RPM
1133
1109
kW
1.37
1.17
1.6
CFM
2558
2208
RPM
1159
1137
kW
1.48
1.20
*
Requires horizontal conversion kit. Please refer to unit TSL for kit number.
Values includes losses for: Unit Casing, 2” Disposable Filters & Dry Evaporator Coil
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
Deduct 250 Cfm for electric heater kits
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 8. Blower Performance for P6SP-072* Units
(6 Ton Horizontal Models Only)