R4GM & R6GN-150* Series
HSD kits:
918799 (208-230V, 3Ø, 60 Hz)
920637 (460V, 3Ø, 60 Hz)
Blower Performance Chart
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open
3.5 Turns
Open
4.0 Turns
Open ‡
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.9
CFM
RPM
kW
1.0
CFM
RPM
kW
1.1
CFM
5350
5100
4850
RPM
1188
1168
1148
kW
3.20
2.98
2.75
1.2
CFM
5225
5000
4700
4400
RPM
1210
1189
1169
1148
kW
3.23
3.00
2.75
2.50
1.3
CFM
5100
4850
4600
4250
3900
RPM
1231
1211
1190
1170
1149
kW
3.25
3.00
2.75
2.53
2.30
1.4
CFM
5300
5050
4800
4500
4200
RPM
1271
1252
1232
1212
1191
kW
3.55
3.33
3.10
2.85
2.60
1.5
CFM
5400
5150
4900
4650
4400
4050
3700
RPM
1313
1293
1273
1253
1233
1213
1192
kW
3.80
3.55
3.30
3.09
2.87
2.59
2.30
1.6
CFM
5375
5000
4725
4450
4175
3900
3600
RPM
1334
1314
1295
1275
1255
1235
1214
kW
3.90
3.60
3.35
3.10
2.86
2.62
2.35
1.7
CFM
5350
4925
4500
4250
4000
RPM
1355
1336
1316
1296
1276
kW
4.00
3.70
3.40
3.15
2.90
1.8
CFM
4850
4475
4100
3725
RPM
1357
1338
1318
1297
kW
3.75
3.48
3.20
2.95
1.9
CFM
4400
4000
3600
RPM
1359
1340
1320
kW
3.50
3.23
2.95
2.0
CFM
RPM
kW
Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 23. Blower Performance for R4GM & R6GN-150* Units
(15 Ton Models Only)