Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual
Page 30
30
R6GP-090*-200C
HSD kits:
920559 (208-230V, 3Ø, 60 Hz)
920558 (460V, 3Ø, 60 Hz)
Horizontal Flow Performance Chart*
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open ‡
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
1.2
CFM
3524
RPM
1160
kW
2.16
1.3
CFM
3495
3344
RPM
1190
1167
kW
2.30
2.08
1.4
CFM
3491
3339
3186
RPM
1220
1196
1171
kW
2.41
2.17
1.93
1.5
CFM
3545
3316
3137
2958
RPM
1247
1226
1202
1178
kW
2.53
2.27
2.07
1.86
1.6
CFM
3391
3145
2941
2736
RPM
1254
1232
1208
1183
kW
2.37
2.14
1.90
1.66
1.7
CFM
3458
3215
2971
2736
RPM
1282
1260
1237
1214
kW
2.54
2.28
2.01
1.74
1.8
CFM
3538
3273
3016
2758
RPM
1313
1289
1265
1241
kW
2.69
2.39
1.92
1.44
1.9
CFM
3383
3123
2840
RPM
1319
1296
1272
kW
2.55
2.24
1.74
2.0
CFM
3543
3447
3181
2915
RPM
1364
1350
1325
1299
kW
2.87
2.65
2.36
2.07
*
Requires horizontal conversion kit. Please refer to unit TSL for kit number.
Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 26. Blower Performance for R6GP-090*-200C Units
(7.5 Ton Horizontal Models Only)