Blower performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual
Page 28
![background image](/manuals/709588/28/background.png)
28
R4GM & R6GN-180* Series
HSD kits:
918800 (208-230/460V, 3Ø, 60 Hz)
Blower Performance Chart
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open
3.5 Turns
Open
4.0 Turns
Open ‡
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.9
CFM
RPM
kW
1.0
CFM
RPM
kW
1.1
CFM
5800
5575
5350
5100
4850
RPM
1228
1208
1188
1168
1148
kW
3.65
3.43
3.20
2.98
2.75
1.2
CFM
6200
5850
5500
5250
5000
4700
4400
RPM
1270
1250
1230
1210
1189
1169
1148
kW
4.1
3.80
3.50
3.25
3.00
2.75
2.50
1.3
CFM
6100
5850
5600
5350
5100
4850
4600
RPM
1309
1290
1271
1251
1231
1211
1190
kW
4.25
4.03
3.80
3.55
3.30
3.03
2.75
1.4
CFM
5800
5550
5300
5050
4800
4500
4200
RPM
1310
1291
1272
1252
1232
1211.5
1191
kW
4.00
3.78
3.55
3.33
3.10
2.85
2.60
1.5
CFM
6000
5700
5400
5150
4900
4650
4400
RPM
1353
1333
1312
1293
1273
1253
1233
kW
4.45
4.13
3.80
3.55
3.30
3.09
2.87
1.6
CFM
5650
5325
5000
4725
4450
RPM
1354
1334
1314
1295
1275
kW
4.25
3.93
3.60
3.35
3.10
1.7
CFM
5350
4925
4500
RPM
1355
1336
1316
kW
4.00
3.70
3.40
1.8
CFM
4850
4475
4100
RPM
1357
1338
1318
kW
3.75
3.48
3.20
1.9
CFM
4400
RPM
1359
kW
3.50
2.0
CFM
RPM
kW
Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 24. Blower Performance for R4GM & R6GN-180* Units
(15 Ton Models Only)