Downfl ow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual
Page 31

31
R6GP-120*-235C
HSD kits:
920395 (208-230V, 3Ø, 60 Hz)
920396 (460V, 3Ø, 60 Hz)
Downfl ow Performance Chart
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open ‡
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.9
CFM
RPM
kW
1.0
CFM
RPM
kW
1.1
CFM
4672
RPM
975
kW
2.65
1.2
CFM
4673
4466
RPM
998
979
kW
2.75
2.50
1.3
CFM
4630
4429
4227
RPM
1018
1000
982
kW
2.90
2.65
2.40
1.4
CFM
4611
4394
4191
3988
RPM
1039
1020
1003
985
kW
2.95
2.70
2.50
2.30
1.5
CFM
4613
4391
4168
3714
3260
RPM
1058
1041
1023
1006
989
kW
3.10
2.85
2.60
2.38
2.15
1.6
CFM
4379
4181
3982
3257
RPM
1061
1046
1031
1012
kW
2.90
2.70
2.50
2.25
1.7
CFM
4480
4233
3976
3718
RPM
1087
1070
1053
1036
kW
3.10
2.80
2.55
2.30
1.8
CFM
4244
3996
3683
3370
RPM
1089
1072
1056
1039
kW
2.90
2.60
2.40
2.20
1.9
CFM
4278
4011
3744
RPM
1111
1093
1075
kW
3.10
2.80
2.50
2.0
CFM
4252
4016
3455
RPM
1130
1115
1097
kW
3.10
2.90
2.50
Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 27. Blower Performance for R6GP-120*-235C Units
(10 Ton Downfl ow Models Only)