Downfl ow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual
Page 13
13
P6SP-090*
MSD kits:
920607 (208-230V, 3Ø, 60 Hz)
920606 (460V, 3Ø, 60 Hz)
Downfl ow Performance Chart
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open ‡
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.8
CFM
3415
3252
3042
2831
RPM
1119
1088
1059
1030
kW
1.92
1.73
1.62
1.50
0.9
CFM
3442
3247
3052
2834
2615
RPM
1150
1121
1092
1063
1033
kW
2.03
1.82
1.62
1.53
1.43
1.0
CFM
3447
3256
3072
2887
2658
2428
RPM
1181
1153
1124
1095
1065
1035
kW
2.11
1.85
1.66
1.47
1.39
1.31
1.1
CFM
3286
3077
2849
2621
RPM
1185
1157
1127
1097
kW
2.00
1.75
1.57
1.39
1.2
CFM
3326
3074
2822
2598
RPM
1215
1189
1162
1133
kW
2.20
1.92
1.64
1.42
1.3
CFM
3320
3064
2856
2647
RPM
1248
1221
1192
1163
kW
2.22
1.92
1.72
1.51
1.4
CFM
3365
3126
2887
2643
RPM
1277
1251
1224
1197
kW
2.32
2.09
1.86
1.57
1.5
CFM
3127
2911
2695
RPM
1283
1255
1227
kW
2.15
1.94
1.73
1.6
CFM
3323
3151
2978
2751
RPM
1340
1313
1286
1259
kW
2.54
2.30
2.05
1.80
Values includes losses for: Unit Casing, 2” Disposable Filters & Dry Evaporator Coil
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
Deduct 250 Cfm for electric heater kits
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 9. Blower Performance for P6SP-090* Units
(7.5 Ton Downfl ow Models Only)