Downfl ow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual
Page 15
15
R6GP-072*-100C
MSD kits:
920609 (208-230V, 3Ø, 60 Hz)
920560 (460V, 3Ø, 60 Hz)
Downfl ow Performance Chart
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open ‡
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.8
CFM
RPM
kW
0.9
CFM
2619
2336
2096
RPM
979
951
924
kW
1.14
0.96
0.86
1.0
CFM
2607
2312
2043
RPM
1008
984
956
kW
1.23
1.06
0.88
1.1
CFM
2535
2332
2010
RPM
1035
1012
988
kW
1.23
1.11
0.88
1.2
CFM
2743
2529
2225
2004
RPM
1089
1065
1039
1016
kW
1.48
1.27
1.06
0.97
1.3
CFM
2475
2231
2042
RPM
1094
1069
1043
kW
1.28
1.13
1.01
1.4
CFM
2512
2176
2046
RPM
1125
1099
1074
kW
1.38
1.16
1.08
1.5
CFM
2450
2266
RPM
1154
1129
kW
4.38
1.23
1.6
CFM
2292
RPM
1159
kW
1.34
Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 11. Blower Performance for R6GP-072* Units
(6 Ton Downfl ow Models Only)