Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual
Page 20
20
R6GP-090*-200C
MSD kits:
920607 (208-230V, 3Ø, 60 Hz)
920606 (460V, 3Ø, 60 Hz)
Horizontal Flow Performance Chart*
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open
2.0 Turns
Open ‡
2.5 Turns
Open
3.0 Turns
Open
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.8
CFM
3310
2993
RPM
1019
979
kW
1.75
1.50
0.9
CFM
3492
3185
2878
RPM
1066
1028
990
kW
1.90
1.65
1.40
1.0
CFM
3549
3339
3020
2700
RPM
1102
1074
1039
1004
kW
2.00
1.80
1.55
1.30
1.1
CFM
3347
3107
2808
2508
RPM
1108
1080
1046
1012
kW
1.90
1.70
1.45
1.20
1.2
CFM
3423
3149
2875
2583
RPM
1140
1112
1084
1053
kW
2.00
1.75
1.50
1.30
1.3
CFM
3435
3223
2950
RPM
1172
1144
1118
kW
2.10
1.80
1.60
1.4
CFM
3502
3196
2889
2668
RPM
1207
1179
1150
1126
kW
2.20
1.95
1.70
1.40
1.5
CFM
3520
3281
2969
2657
RPM
1238
1212
1184
1155
kW
2.40
2.10
1.85
1.60
1.6
CFM
3317
3063
2776
RPM
1242
1216
1189
kW
2.25
2.00
1.75
*
Requires horizontal conversion kit. Please refer to unit TSL for kit number.
Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 16. Blower Performance for R6GP-090*-200C Units
(7.5 Ton Horizontal Models Only)