Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual
Page 14
![background image](/manuals/709588/14/background.png)
14
P6SP-090*
MSD kits:
920607 (208-230V, 3Ø, 60 Hz)
920606 (460V, 3Ø, 60 Hz)
Horizontal Flow Performance Chart*
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open ‡
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.8
CFM
3411
3228
3136
3043
RPM
1053
1025
1013
1000
kW
1.98
1.78
1.68
1.58
0.9
CFM
3309
3131
3005
2878
RPM
1065
1039
1022
1005
kW
1.94
1.75
1.59
1.43
1.0
CFM
3410
3221
3031
2851
2670
RPM
1110
1083
1055
1032
1009
kW
2.07
1.89
1.70
1.54
1.38
1.1
CFM
3321
3114
2906
2681
2455
RPM
1122
1096
1070
1043
1015
kW
2.03
1.84
1.64
1.46
1.27
1.2
CFM
3423
3198
2964
2729
2492
RPM
1162
1132
1103
1074
1046
kW
2.17
1.91
1.56
1.20
1.20
1.3
CFM
3268
3033
2783
2533
RPM
1169
1140
1110
1080
kW
2.12
1.84
1.63
1.41
1.4
CFM
3347
3106
2864
2590
2315
RPM
1203
1174
1145
1115
1085
kW
2.26
2.01
1.75
1.56
1.36
1.5
CFM
3399
3174
2924
2673
RPM
1231
1206
1178
1149
kW
2.37
2.08
1.86
1.63
1.6
CFM
3235
2993
RPM
1236
1210
kW
2.23
1.98
*
Requires horizontal conversion kit. Please refer to unit TSL for kit number.
Values includes losses for: Unit Casing, 2” Disposable Filters & Dry Evaporator Coil
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
Deduct 250 Cfm for electric heater kits
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 10. Blower Performance for P6SP-090* Units