Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual
Page 26
![background image](/manuals/709588/26/background.png)
26
Q6SP-090* & Q5SN-090*
HSD kits:
920394 (208-230V, 3Ø, 60 Hz)
920608 (460V, 3Ø, 60 Hz)
Horizontal Flow Performance Chart*
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open ‡
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.9
CFM
RPM
kW
1.0
CFM
RPM
kW
1.1
CFM
3890
RPM
891
kW
1.93
1.2
CFM
4140
3883
3625
RPM
937
915
893
kW
2.28
2.05
1.82
1.3
CFM
3910
3585
3260
RPM
939
918
897
kW
2.15
1.91
1.66
1.4
CFM
4150
3895
3640
RPM
983
963
942
kW
2.45
2.23
2.00
1.5
CFM
3940
3595
3250
RPM
985
965
945
kW
2.33
2.08
1.82
1.6
CFM
3630
RPM
988
kW
2.15
1.7
CFM
3960
3355
2750
RPM
1031
1014
996
kW
2.52
2.13
1.74
1.8
CFM
3690
RPM
1035
kW
2.35
1.9
CFM
3975
3388
2800
RPM
1073
1059
1044
kW
2.73
2.33
1.92
2.0
CFM
3059
RPM
1083
kW
2.22
*
Requires horizontal conversion kit. Please refer to unit TSL for kit number.
Values includes losses for: Unit Casing, 2” Disposable Filters & Dry Evaporator Coil
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
Deduct 250 Cfm for electric heater kits
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 22. Blower Performance for Q6SP-090* & Q5SN-090* Units
(7.5 Ton Horizontal Models Only)