Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual
Page 16
16
R6GP-072*-100C
MSD kits:
920609 (208-230V, 3Ø, 60 Hz)
920560 (460V, 3Ø, 60 Hz)
Horizontal Flow Performance Chart*
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open ‡
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.8
CFM
RPM
kW
0.9
CFM
2618
2403
2188
RPM
975
948
920
kW
1.12
0.98
0.84
1.0
CFM
2577
2367
2073
1865
RPM
1006
980
952
924
kW
1.17
0.99
0.88
0.70
1.1
CFM
2562
2361
2085
RPM
1037
1006
983
kW
1.21
1.07
0.93
1.2
CFM
2575
2328
2085
RPM
1062
1041
1011
kW
1.31
1.10
0.95
1.3
CFM
2601
2356
2048
RPM
1094
1066
1045
kW
1.36
1.18
0.98
1.4
CFM
2580
2357
2126
RPM
1122
1099
1071
kW
1.46
1.25
1.12
1.5
CFM
2569
2323
2129
RPM
1149
1125
1104
kW
1.51
1.33
1.16
1.6
CFM
2307
RPM
1154
kW
1.37
*
Requires horizontal conversion kit. Please refer to unit TSL for kit number.
Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 12. Blower Performance for R6GP-072* Units
(6 Ton Horizontal Models Only)