Horizontal flow performance chart – Reznor R6GN Option - Installation - High Static Blower Drive - Light Commercial User Manual
Page 18
![background image](/manuals/709588/18/background.png)
18
R6GP-072*-166C
MSD kits:
920613 (208-230V, 3Ø, 60 Hz)
920618 (460V, 3Ø, 60 Hz)
Horizontal Flow Performance Chart*
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open ‡
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.8
CFM
RPM
kW
0.9
CFM
2755
2510
2265
RPM
981
956
930
kW
1.18
1.04
0.90
1.0
CFM
2732
2511
2240
1968
RPM
1013
987
960
933
kW
1.28
1.09
0.95
0.81
1.1
CFM
2714
2470
2225
RPM
1042
1017
991
kW
1.31
1.14
0.98
1.2
CFM
2708
2456
2214
RPM
1073
1047
1021
kW
1.41
1.21
1.02
1.3
CFM
2722
2446
2170
RPM
1103
1077
1051
kW
1.44
1.26
1.08
1.4
CFM
2696
2454
2204
RPM
1131
1105
1082
kW
1.54
1.31
1.11
1.5
CFM
2706
2473
2351
RPM
1159
1137
1107
kW
1.54
1.36
1.23
1.6
CFM
2713
2426
2232
RPM
1187
1166
1143
kW
1.66
1.43
1.27
*
Requires horizontal conversion kit. Please refer to unit TSL for kit number.
Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 14. Blower Performance for R6GP-072*-166C Units
(6 Ton Horizontal Models Only)