Appendix A:
Simon XT TableTop Control Panel Installation Manual
75
Function
Programming page
reference
Default setting Required setting
Autoarm
Table 11 on page 39
On
On
Unvacated premises
Table 18 on page 48
On
On
Call waiting
Table 13 on page 41
Off
On if reporting to central
station and customer has call
waiting service
Exit extension
Table 11 on page 39
On
On
Swinger shutdown
Table 16 on page 45
On (one trip)
On (one trip)
Fire alarm verify
Table 16 on page 45
Off
On
Duress/panic code
Table 10 on page 38
Disabled
Disabled
Cross zone
“Cross-zoning” on
page 12
Disabled
Disabled for zones with high
probability of false alarms.
Table 37 below describes nonprogrammable (hard-coded) system operation, as
required to meet ANSI-SIA CP-01, and is provided only for your reference.
Table 37: Non programmable (hard coded) system operation
Function
Operation
Silent exit
All annunciators enabled
Remote arming exit
time and progress
annunciation
All annunciators enabled
Abort annunciation
Enabled
Cancel report
annunciation
Enabled
Recent closing
Enabled (2 minute window)
Exit error
Enabled
Restoration of power
Panel resumes operation in same arming state and disregards alarm
signals from sensors for the first 60 seconds after power restoration
Cancel alarm
Enter code only.
Note: During a two-way voice session, additional alarms will be indicated at the
panel immediately and reported to the Central Station as soon as the session
ends.