Interfacing, Setup and calibration, Profinet setup – Flintec FAD-30 User Manual
Page 39
FAD-30 Technical Manual, Rev. 1.06 December 2012
Page 39 of 48
Load Cell Connection
See chapter 4.4.2
Power Supply Connection
See chapter 4.2.1
8.3. Interfacing
FAD-30PN instruments have two interface connectors on the front of the instrument: ProfiNet and RS-232C.
The table below describes the data formats for interfacing the peripherals and their application.
Data Format
Description
Application
Hardware
ProfiNet
ProfiNet interfacing.
Refer to chapter 5.11
Interfacing with PLC.
ProfiNet
Table 8.3
– Data output interfacing
Attention: Please disable the interface you will not use to increase the performance of the instrument.
8.4. Setup and Calibration
FAD-30PN instruments are set up and calibrated by xFace. The A/D Converter settings are very important for a
good weighing performance. Please refer to chapter 5.3.
8.5. ProfiNet Setup
The ProfiNet setup is done by xFace software as described in this chapter. Select the Gateway tab after
connecting xFace to the instrument. You will see the ProfiNet parameters in this tab.
ProfiNet Setup
There are 7 setup parameters for ProfiNet network.
DHCP
Dynamic Host Configuration Protocol automates network parameters if it is enabled.
Default is „Disable‟.
IP Address
If DHCP is disabled, define IP address manually. Default is „192.168.16.250‟
Subnet Mask
If DHCP is disabled, define subnet mask manually. Default is „255.255.255.0‟.
Default Gateway If DHCP is disabled, define default gateway manually
. Default is „192.168.16.254‟.
Primary DNS
If DHCP is disabled, define primary DNS manually. Default is „208.67.222.222‟.
Secondary DNS
If DHCP is disabled, define secondary DNS manually. Default is „208.67.220.220‟.
Host Name
Enter a unique host name t
o the instrument. Default is „ ‟
ProfiNet Data Structure
Please refer to chapter 5.11