Plc output to fad-30px input, Plc output to fad-30px input 2, Dword – Flintec FAD-30 User Manual
Page 27: Plc output to fad-30px input 3
FAD-30 Technical Manual, Rev. 1.06 December 2012
Page 27 of 48
PLC Output to FAD-30Px Input
Dword
D31 D30 D29 D28 D27 D26 D25 D24 D23 D22 D21 D20 D19 D18 D17 D16
D15 D14 D13 D12 D11
D10
D9
D8
D7
D6
D5
D4
D3
D2
D1
D0
1
st
Dword
Not in use
2
nd
Dword
W31
MSB
W30 W29 W28 W27 W26 W25 W24 W23 W22 W21 W20 W19 W18 W17 W16
W15 W14 W13 W12 W11 W10 W9
W8
W7
W6
W5
W4
W3
W2
W1
W0
LSB
3
rd
Dword
Not in use
Not in use
Command List
Data Selection
New
CMD
PLC Output to FAD-30Px Input 2
nd
Dword
The 2
nd
Dword contains
the setting / parameter value (Refer to “Command List”, see PLC Output to FAD-30Px
Input 3rd Dword).
PLC Output to FAD-30Px Input 3
rd
Dword
Bit no.
3
rd
Dword descriptions
D31…D11
Not in use
D10…D6
Command
list
00000
No command is activated
00001
Zero
00010
Tare
00011
Clear
00101
Adjust zero calibration
00110
Adjust span calibration (First load calibration weight on scale then load
2
nd
Dword with span test weight value*, then apply this command with
New CMD)
01000
Operation mode selection (First
load 2
nd
Dword with selected
value, then apply this command
with New CMD)
Load 2
nd
Dword with one of these:
0: Count mode unipolar
1: Count mode bipolar
2: Force mode unipolar
3: Force mode bipolar
4: Weight mode unipolar
01001
mV operation in Count Mode
(First load 2
nd
Dword with
selected value, then apply this
command with New CMD)
Load 2
nd
Dword with one of these:
0: 5 mV
1: 10 mV
2: 15 mV
3: 18 mV
01010
Digital filter
(First load 2
nd
Dword with
selected value, then apply this
command with New CMD)
Load 2
nd
Dword with one of these:
0: Fast
…
5: Medium
…
…
7: Default
…
9: Slow
D5...D1
Read
selected
data
00000
Indicated weight
00001
Gross weight
00010
Tare weight
00011
Indicated weight (Floating point)
00100
Gross weight (Floating point)
00101
Tare weight (Floating weight)
10000
Calibration status
D0
New CMD Apply commands which are listed in
“Command list” (Responds on bit changes)
*Span test weight value has to be entered ignoring the decimal point;
e.g. “300.00” has to be entered as “30000”