FAD-30 Technical Manual, Rev. 1.06 December 2012

Page 26 of 48

Calibration Status

Bit no.

2

nd

Dword descriptions when read command is ‘Calibration Status’.

Refer to PLC Output to FAD-30Px Input 3

rd

Dword

D31…D16

Not in use

D15…D8

Calibration
error

0000 0001

Calibration timeout: - Restart calibration

0000 0010

ADC error: - Re-energize the instrument

0000 0011

Instrument cannot be calibrated
- Check load cell cable; - Re-energize the instrument

0010 0010

Instrument cannot be calibrated
- Load cell signal is very low or too high

0010 0011

Calibration Error
- Calibration test weight is too small; Increase calibration weight
value (Write test weight value from PLC Output to FAD-30Px Input
2

nd

Dword then restart the calibration)

- Check load cell connections

0010 0101

Scale unstable: - Wait until scale becomes stable
- Check ground wiring

D7...D0

Calibration
process
status

0000 0001

System ready for calibration

0000 0011

Zero calibration in process

0000 0100

Span calibration in process

0000 1001

Error (Calibration error)