3.4

General characteristics

Applicable safety regulations

EN60730-1

Purpose of the device

Programmable electronic controller for
refrigeration, ventilation and air-
conditioning applications

Storage conditions

-10~70°C Condensation free RH <80%

Operating conditions

-10~50°C Condensation free RH <80%

Electric shock protection class

Control device to be integrated; assumes
the class of the integrated equipment

Disconnection type

Reduced interruption (relay contacts)

PTI of insulation materials

>=250V

Case

Mounted on omega rails

Action type

1C

Pollution

Normal

Software class

A

Isolated component electrical stress period

Long

Front panel protection classification

IP00 for open case versions; otherwise IP
40


3.5

Technical characteristics

Low voltage signal connection

Phoenix detachable terminal block;
screw terminal blocks for open case
versions

Power connector

Phoenix detachable terminal block;
screw terminal blocks for open case
versions

Cable cross sectional thickness >
0.75mm

2

Connection for EVCO live serial port to remote keypad
and/or remote I/O expansion card

Phoenix detachable terminal block;
screw terminal blocks for open case
versions

Connection for parameter key, TTL serial output for RS-
485 module, Flash programming interface

AMP micro-match 6 pin

D/A output connection

Phoenix detachable terminal block;
screw terminal blocks for open case
versions