beautypg.com

EVCO EPK4BHQ1AH Hardware manual User Manual

Page 49

background image

EVCO S.p.A.

c-pro 3 NODE kilo+ | Hardware manual ver. 1.0 | Code 114CP3NKPE104

page 49 of 55

Power supply:

-

24 VAC (+10 %, -15 %), 50/60 Hz (±3 Hz), 35 VA max. non insulated

-

24 VDC (-15 %, +65 %), 12 W max. non insulated

supplied by a class 2 circuit.

Protect the power supply with a 2A-T 250 V fuse

If the device runs on direct current, it shall be necessary to pay attention to the polarity of

the supply voltage.

Rated impulse voltage:

4 KV.

Overvoltage category:

III.

Class and structure of software:

A.

Clock:

integrated (with primary lithium battery)

Battery autonomy without power supply: 5 years at 25 °C (77 °F).

Drift: ≤ 30 s/ month at 25 °C (77 °F).

Analog inputs:

10 inputs:

-

4 configurable via configuration parameter for PTC, NTC or Pt 1000 probes

-

6 configurable via configuration parameter for PTC, NTC, Pt 1000 probes,

transducers 0-20 mA, 4-20 mA, 0-5 V ratiometric or 0-10 V.

Ratiometric transducers 0-5 V power supply: 5 VDC (+0 %, -12 %), 60 mA max.

Transducers power supply 0-20 mA, 4-20 mA e 0-10 V: 12 DC (+50 %, -25 %),

120 mA max.

The maximum current distributable by the two power supplies is 120 mA.

Digital inputs PTC (990 @ 25 °C, 77 °F)

Type of sensor:

KTY 81-121.

Measurement field:

from -50 to 150 °C (from -58 to 302 °F).

Precision:

±0,5 % of scale end.

Resolution :

0,1 °C.

Conversion time:

100 ms.

Protection:

none.

Digital inputs NTC (10 K @ 25 °C, 77 °F)

Type of sensor:

ß3435.

Measurement field:

from -50 to 120 °C (from -58 to 248 °F).

Precision:

-

±0.5 % of scale end from -40 to 100 °C

-

±1 °C from -50 to -40 °C and from 100 to 120 °C.

Resolution :

0.1 °C.

Conversion time:

100 ms.

Protection:

none.