EVCO EPK4BHQ1AH Hardware manual User Manual
Page 18

EVCO S.p.A.
c-pro 3 NODE kilo+ | Hardware manual ver. 1.0 | Code 114CP3NKPE104
page 18 of 55
ANALOG INPUTS / OUTPUTS
Analog inputs and outputs
Please see paragraph 6 "CONFIGURATION" for the settings of the analog inputs and outputs.
PART
MEANING
GND
analog inputs and outputs ground
AI7
analog input 7 settable by way of the PTC, NTC, Pt 1000 probes configuration parameter, transducers 0-20 mA, 4-20
mA, 0-5 V ratiometric or 0-10 V
AI8
analog input 8 settable by way of the PTC, NTC, Pt 1000 probes configuration parameter, transducers 0-20 mA,
4-20 mA, 0-5 V ratiometric o 0-10 V
AI9
analog input 9 settable by way of the PTC, NTC, Pt 1000 probes configuration parameter, transducers 0-20 mA,
4-20 mA, 0-5 V ratiometric o 0-10 V
AI10
analog input 10, settable by way of the PTC, NTC, Pt 1000 probes configuration parameter
GND
analog inputs and outputs ground
AO4
analog output 4, settable by way of the configuration parameter for 0-20 mA, 4-20 mA or 0-10 V
AO5
analog output 5, for 0-10 V
AO6
analog output 6, for 0-10 V
DIGITAL OUTPUTS
Digital outputs.
PART
MEANING
CO1
common digital output 1
NO1
usually open contact for digital output 1
according to model:
-
electromechanical relay with 3 A res. @ 250 VAC
-
control for 24 VAC/DC, 600 mA max. solid state relays
CO2
common digital output 1
NO2
usually open contact for digital output 2
according to model:
-
electromechanical relay with 3 A res. @ 250 VAC
-
control for 24 VAC/DC, 600 mA max. solid state relays
CO3-6
common digital output 3... 6
NO3
usually open contact for digital output 3 (electromechanical relay with 3 A res. @ 250 VAC)
NO4
usually open contact for digital output 4 (electromechanical relay with 3 A res. @ 250 VAC)